Zigzag Grounding Systems
1. Definition and Purpose of Zigzag Grounding
1.1 Definition and Purpose of Zigzag Grounding
A zigzag grounding system is a specialized transformer winding configuration designed to provide a low-impedance path for zero-sequence currents while maintaining high impedance to positive- and negative-sequence currents. This unique property makes it particularly useful in power systems for grounding unbalanced loads, mitigating fault currents, and stabilizing neutral voltages.
Fundamental Configuration
The zigzag transformer consists of six windings arranged in two sets of three-phase windings, each wound in an alternating (zigzag) pattern. The windings are interconnected such that each phase winding is split into two halves, with one half wound on one core leg and the other half on an adjacent leg. The neutral point is formed at the junction of these windings, providing a grounding reference.
The voltage phasor relationship in a zigzag transformer can be derived as follows:
where Van, Vbn, Vcn are the phase-to-neutral voltages, and Va1, Va2, Vb1, Vb2, Vc1, Vc2 represent the voltages across the two halves of each winding.
Purpose and Advantages
The primary purposes of zigzag grounding include:
- Neutral Stabilization: Provides a stable neutral point in ungrounded or floating systems, preventing overvoltages during ground faults.
- Fault Current Limitation: Offers a low-impedance path for zero-sequence currents, allowing sufficient fault current for protective relay operation while limiting excessive currents.
- Harmonic Mitigation: Reduces third-harmonic currents by providing a circulating path, improving power quality.
- Grounding of Unbalanced Loads: Facilitates the grounding of single-phase or unbalanced loads in three-phase systems.
Mathematical Analysis of Zero-Sequence Impedance
The zero-sequence impedance (Z0) of a zigzag transformer is significantly lower than its positive-sequence impedance (Z1). The relationship can be expressed as:
where Zm is the mutual impedance between windings. For an ideal zigzag transformer with perfect coupling, Z0 approaches a very low value, making it highly effective for grounding applications.
Practical Applications
Zigzag grounding is commonly used in:
- Industrial Power Systems: To mitigate ground faults in facilities with sensitive equipment.
- Renewable Energy Systems: For grounding solar and wind power inverters where neutral stability is critical.
- Marine and Offshore Installations: To ensure safety and reliability in isolated power systems.
In real-world applications, the zigzag transformer's ability to handle unbalanced conditions without requiring a separate grounding source makes it a preferred choice in many power distribution scenarios.
1.2 Key Components and Configuration
Fundamental Structure of a Zigzag Grounding System
A zigzag grounding system consists of interconnected conductors arranged in a non-linear, alternating pattern to achieve low-impedance earth coupling. The primary components include:
- Grounding Electrodes: Typically made of copper-clad steel or galvanized rods, driven vertically into the earth at specified intervals.
- Interconnecting Conductors: Bare copper wires or strips forming the zigzag pattern, with cross-sectional area determined by fault current requirements.
- Junction Points: Exothermic welded or compression-lug connections ensuring low-resistance joints between conductors and electrodes.
Mathematical Basis for Configuration
The optimal angle (θ) between zigzag segments balances surface area coverage and material efficiency. For a given electrode spacing d, the effective grounding resistance Rg is minimized when:
where Ï is soil resistivity, L is electrode length, a is electrode radius, and S is system area. The 60° zigzag angle proves optimal when:
Practical Implementation Considerations
Field measurements from substation installations show that zigzag systems reduce ground potential rise by 30-40% compared to radial configurations. Key installation parameters include:
- Depth: 0.5-1.0 m below frost line to maintain consistent soil contact
- Conductor Sizing: Minimum 70 mm² copper for 25 kA fault currents
- Electrode Spacing: 3-5 times electrode length to prevent mutual interference
High-Frequency Performance Characteristics
At frequencies above 1 MHz, the zigzag configuration exhibits distributed transmission line behavior. The characteristic impedance Z0 between parallel conductors is given by:
where D is conductor separation, d is conductor diameter, and εeff is the effective dielectric constant of surrounding soil. This property makes zigzag systems particularly effective for lightning impulse dispersion.
1.3 Comparison with Other Grounding Methods
Zigzag grounding systems exhibit distinct advantages and trade-offs when compared to traditional grounding methods such as solid grounding, resistance grounding, and reactance grounding. The key differentiating factors include fault current magnitude, transient overvoltage suppression, system stability, and cost-effectiveness.
Fault Current Characteristics
In a zigzag grounding system, the zero-sequence impedance is intentionally designed to limit ground fault currents while maintaining system stability. The fault current If in a zigzag transformer can be derived from the zero-sequence impedance Z0:
where VLL is the line-to-line voltage. Compared to solid grounding, which allows fault currents as high as three-phase short-circuit levels, zigzag grounding restricts If to 10–20% of the maximum fault current, reducing equipment stress.
Transient Overvoltage Mitigation
Unlike ungrounded or high-resistance grounded systems, zigzag grounding effectively suppresses transient overvoltages caused by arcing faults. The zigzag transformer’s winding configuration provides a low-impedance path for zero-sequence currents, preventing voltage escalation during line-to-ground faults. This contrasts with reactance grounding, where inductive components may exacerbate transient overvoltages under certain conditions.
System Stability and Fault Localization
Zigzag grounding offers superior fault localization compared to resistance grounding. The inherent asymmetry in zero-sequence current distribution enables precise relay coordination, isolating faults without unnecessary tripping of healthy feeders. However, it requires careful tuning of protective relays to avoid misoperation during high-impedance faults—a challenge less pronounced in solidly grounded systems.
Cost and Implementation Complexity
While zigzag transformers have higher initial costs than simple resistance grounding systems, their long-term maintenance requirements are lower. The absence of external resistors eliminates thermal degradation issues, making zigzag grounding preferable for industrial plants with continuous operation demands. However, in systems requiring rapid fault clearing (e.g., high-voltage transmission), solid grounding remains dominant due to its simplicity.
Comparative Summary
- Solid Grounding: High fault currents, simple protection, but increased equipment damage risk.
- Resistance Grounding: Limited fault current, but susceptible to transient overvoltages.
- Reactance Grounding: Compromise between current limitation and overvoltage control, but requires precise tuning.
- Zigzag Grounding: Optimal balance of fault current limitation, overvoltage suppression, and system stability at higher complexity.
2. Impedance and Fault Current Behavior
2.1 Impedance and Fault Current Behavior
The impedance characteristics of a zigzag grounding system play a critical role in determining its effectiveness during fault conditions. Unlike conventional grounding methods, the zigzag transformer introduces a unique impedance profile that selectively suppresses zero-sequence currents while allowing positive and negative sequence currents to pass.
Impedance Characteristics
The zero-sequence impedance Z0 of a zigzag transformer is primarily determined by its winding configuration and core design. For an ideal zigzag transformer with perfect coupling between windings, the zero-sequence impedance can be expressed as:
where Zφ represents the per-phase leakage impedance and Zn is the neutral grounding impedance. In practice, the zigzag connection creates a high-impedance path for zero-sequence currents while maintaining low impedance for positive and negative sequence components.
Fault Current Distribution
During a line-to-ground fault, the fault current If divides between the zigzag transformer and parallel paths according to their respective impedances. The fault current through the zigzag winding is given by:
where Vph is the phase voltage and Zf represents the fault impedance. This relationship shows how the zigzag transformer limits ground fault currents while maintaining system stability.
Practical Considerations
Several factors influence the real-world behavior of zigzag grounding systems:
- Core saturation: Under severe fault conditions, magnetic saturation can reduce the effective zero-sequence impedance
- Harmonic distortion: The nonlinear impedance characteristic may generate harmonics during faults
- Neutral grounding resistance: Additional impedance in the neutral path further limits fault currents but affects system sensitivity
Transient Response Analysis
The dynamic behavior of zigzag grounding systems during fault initiation involves complex interactions between electromagnetic transients and system capacitance. The initial transient current can be modeled as:
where Iss is the steady-state fault current, Idc represents the DC offset component, and Ï„ is the system time constant determined by the X/R ratio.
Modern power systems often incorporate zigzag grounding in conjunction with other protection schemes, requiring careful coordination of relay settings to account for the unique impedance characteristics. Field measurements from industrial installations show that properly designed zigzag systems can reduce ground fault currents by 60-80% compared to solidly grounded systems.
2.2 Harmonic Mitigation Capabilities
Zigzag grounding systems exhibit unique harmonic suppression characteristics due to their inherent impedance properties and winding configuration. The transformer's zero-sequence impedance (Z0) plays a critical role in attenuating triplen harmonics (3rd, 9th, 15th, etc.), which are predominantly zero-sequence currents. The mitigation mechanism arises from the following factors:
Impedance to Zero-Sequence Currents
The zigzag winding creates a low-impedance path for zero-sequence currents while presenting high impedance to positive- and negative-sequence components. The zero-sequence impedance (Z0) is derived from the mutual coupling between windings and can be expressed as:
where Zm is the mutual impedance between windings and Zleakage is the leakage impedance. This forces triplen harmonics to circulate within the transformer rather than propagating into the system.
Harmonic Flux Cancellation
The phase-shifted winding arrangement (typically 120° displacement) induces opposing magnetic fluxes for harmonic frequencies. For the 3rd harmonic, the fluxes cancel in the core, reducing harmonic voltage distortion. The cancellation efficiency (ηh) for a harmonic of order h is given by:
where X0 is the zero-sequence reactance and R0 is the resistive component.
Practical Applications
- Industrial Power Systems: Zigzag transformers are deployed in variable-frequency drive (VFD) installations to mitigate harmonics injected into the grid.
- Renewable Energy: Used in solar/wind farms to suppress inverter-generated harmonics before they reach the utility interface.
- Data Centers: Critical for maintaining power quality in IT infrastructure with nonlinear loads.
Case Study: Harmonic Attenuation in a 480V System
A zigzag grounding transformer reduced 3rd harmonic distortion from 12% to 2.3% in a semiconductor fabrication plant. The system parameters were:
2.3 Transient Response Analysis
The transient response of a zigzag grounding system governs its behavior under fast-rising surge events, such as lightning strikes or switching transients. Unlike steady-state analysis, transient modeling must account for distributed parameters, including inductance (L), capacitance (C), and frequency-dependent soil ionization effects.
Distributed Parameter Model
A multi-conductor transmission line (MTL) approach captures the frequency-dependent impedance of zigzag electrodes. The telegrapher's equations for a lossy line are:
Where R and G represent soil resistance and leakage conductance per unit length. For zigzag configurations, mutual coupling between parallel electrode segments introduces off-diagonal terms in the impedance matrix.
Time-Domain Solution Methods
Three primary techniques are employed for solving these equations:
- Finite Difference Time Domain (FDTD): Discretizes space and time using Yee's algorithm, suitable for nonlinear soil breakdown modeling.
- Modal Decomposition: Diagonalizes the MTL equations via eigenvalue analysis, reducing computational complexity.
- Vector Fitting: Approximates frequency-dependent parameters with rational functions for efficient inverse Laplace transforms.
Soil Ionization Effects
Under high-current conditions (>10 kA), soil conductivity increases nonlinearly due to plasma formation. The dynamic resistivity follows:
Where Ec is the critical electric field (~300 kV/m for typical soils) and E(t) is the instantaneous field strength.
Validation Case Study
Field measurements from a 138 kV substation grounding grid show close agreement with FDTD simulations when including:
- Frequency-dependent conductor skin effects
- Non-uniform soil layering (2-layer model)
- Time-varying ionization parameters
Optimization Guidelines
To improve transient response:
- Minimize acute angles in zigzag paths to reduce local inductance
- Implement gradient rings at perimeter to equalize potential rise
- Use supplemental vertical rods at nodes to enhance high-frequency dispersion
Where τeff characterizes the cumulative time constant of N parallel current paths.
3. Sizing and Selection of Zigzag Transformers
3.1 Sizing and Selection of Zigzag Transformers
Fundamentals of Zigzag Transformer Impedance
The impedance of a zigzag transformer plays a critical role in its ability to limit fault currents while maintaining system stability. The zero-sequence impedance (Z0) is particularly important, as it determines the transformer's effectiveness in grounding applications. For a balanced system, the zero-sequence impedance can be derived from the transformer's winding configuration and per-unit leakage reactance.
where Zn represents the neutral grounding impedance and Zleakage is the transformer's inherent leakage impedance. The factor of 3 arises due to the zero-sequence current summation in all three phases.
Core Sizing and Magnetic Considerations
Zigzag transformers require careful core sizing to handle the unique flux patterns generated by their winding arrangement. Unlike conventional transformers, zigzag configurations exhibit:
- Asymmetric flux distribution due to phase displacement
- Higher harmonic content requiring derating considerations
- Increased core losses from zero-sequence components
The core cross-sectional area (Acore) must account for these factors through the modified voltage equation:
where kzigzag (typically 0.86-0.92) compensates for the winding arrangement's flux inefficiency.
Current Rating and Thermal Design
The continuous current rating must consider both balanced load conditions and unbalanced fault scenarios. The worst-case thermal stress occurs during single-line-to-ground faults, where the current in one winding can reach:
Practical designs incorporate a 150-200% short-time overload capacity for 10-second durations. Cooling requirements are typically 15-20% more stringent than equivalent delta-wye transformers due to additional eddy current losses in the zigzag configuration.
Voltage Ratio and Winding Design
The turns ratio between zig and zag windings must maintain precise symmetry to prevent voltage unbalance. The ideal ratio follows:
Winding resistance matching should be within 0.5% to prevent circulating currents. Practical implementations often use bifilar winding techniques to ensure tight coupling and minimize leakage flux.
Practical Selection Guidelines
When specifying zigzag transformers for grounding applications:
- System voltage: Select based on line-to-line voltage, not phase voltage
- Fault current: Size for maximum available fault current with 25% margin
- Impedance: Target 8-12% impedance for most industrial systems
- Insulation class: Use 125% of system basic insulation level (BIL)
Modern designs often incorporate additional taps (±5%) to accommodate system impedance variations. For harmonic-rich environments, K-factor rated designs (typically K-4 to K-13) are recommended.
Case Study: 34.5kV Industrial Installation
A petrochemical plant required a zigzag grounding transformer for their 34.5kV system with 12kA fault current. The selected parameters were:
Parameter | Value |
---|---|
Rated Voltage | 34.5kV (20kV BIL) |
Continuous Current | 400A (600A for 10s) |
Zero-Sequence Impedance | 9.8% (0.98Ω) |
Cooling | ONAN/ONAF (OA/FA) |
Field measurements confirmed the design limited ground faults to 850A while maintaining voltage unbalance below 1.2% during normal operation.
3.2 Installation Best Practices
Soil Resistivity Analysis
Prior to installation, conduct a four-point Wenner array test to measure soil resistivity (Ï). The measured resistivity directly impacts the grounding system's effectiveness and determines conductor spacing requirements. For a Wenner array with probe spacing a, the resistivity is calculated as:
Where V is the measured voltage and I is the injected current. Perform measurements at multiple locations and depths to account for soil stratification.
Conductor Layout Optimization
The zigzag pattern reduces mutual coupling between conductors while maintaining low impedance. Key geometric parameters include:
- Vertex angle (θ): Optimal between 90°-120° for balanced current distribution
- Conductor spacing (s): Typically 1-2 times burial depth to prevent overlapping potential gradients
- Segment length (L): Should exceed 6m to ensure proper current dispersion
Material Selection Criteria
Use high-conductivity materials with adequate corrosion resistance:
- Copper: ≥ 25mm² cross-section for main conductors
- Copper-bonded steel: For areas with mechanical stress
- Exothermic welds: Required for all permanent joints
Burial Depth Considerations
The minimum burial depth (d) must satisfy:
Where Ifault is maximum fault current, t is fault duration, and K is material constant (247 for copper). In permafrost regions, install below the frost line with bentonite backfill.
Testing and Validation
After installation, perform:
- Fall-of-potential tests: Verify impedance meets design specifications
- Current injection tests: Confirm uniform current distribution across all segments
- Thermal imaging: Identify hotspots during fault conditions
The measured impedance Zg should satisfy:
Where Vstep is the permissible step voltage (typically 5kV for industrial installations).
3.3 Common Pitfalls and How to Avoid Them
Incorrect Conductor Spacing
A frequent error in zigzag grounding systems is improper spacing between conductors. If the spacing is too wide, the grounding impedance increases, reducing the system's effectiveness in fault dissipation. Conversely, excessively narrow spacing leads to mutual inductance coupling, which can induce unwanted circulating currents. The optimal spacing d between conductors is derived from the electromagnetic field interaction:
where μ0 is the permeability of free space, I is the maximum fault current, and B is the allowable magnetic flux density. For most soil conditions, maintaining d between 1.5–3 meters balances impedance and coupling effects.
Poor Soil Resistivity Management
Ignoring soil resistivity variations is a critical oversight. The grounding resistance Rg of a zigzag system depends on soil resistivity Ï and the geometric arrangement:
Here, L is the conductor length, and r is the radius of the conductor. To mitigate high resistivity:
- Use soil enhancement materials (e.g., bentonite or conductive backfill) in areas with Ï > 100 Ω·m.
- Implement deep-ground electrodes to reach lower-resistivity strata.
Inadequate Corrosion Protection
Corrosion in buried conductors compromises long-term performance. Galvanic corrosion occurs due to dissimilar metals or stray DC currents. The corrosion rate k follows Faraday's law:
where Ic is the corrosion current, M is the molar mass, n is the valence, F is Faraday's constant, and Ïm is the metal density. Mitigation strategies include:
- Sacrificial anodes (e.g., magnesium or zinc) for cathodic protection.
- Coating conductors with epoxy or polyethylene.
Negging Transient Overvoltage Protection
Zigzag systems are vulnerable to lightning strikes and switching surges. The transient voltage Vt across the grounding system is:
where L is the inductance, di/dt is the rate of current change, and R is the resistance. To suppress transients:
- Install surge arresters at critical nodes.
- Use low-inductance conductor layouts (e.g., radial rather than parallel paths).
Fault Current Miscalculations
Underestimating fault currents leads to undersized conductors. The prospective fault current If in a zigzag system is:
where Vph is the phase voltage, Zs is the source impedance, and Zg is the grounding impedance. Always:
- Model worst-case scenarios using IEC 60909 or IEEE 80 standards.
- Verify conductor thermal withstand via I2t calculations.
4. Use in Industrial Facilities
4.1 Use in Industrial Facilities
Zigzag grounding systems are widely adopted in industrial facilities due to their ability to mitigate ground potential rise (GPR) and reduce electromagnetic interference (EMI) in high-power environments. Unlike conventional grounding methods, the zigzag configuration distributes fault currents more evenly, minimizing localized voltage gradients that could endanger personnel or damage sensitive equipment.
Fault Current Distribution
In industrial settings, fault currents can reach magnitudes exceeding tens of kiloamperes. The zigzag grounding topology ensures that fault currents are distributed across multiple parallel paths, reducing the effective impedance seen by the fault. The equivalent impedance Zeq of an N-branch zigzag system is given by:
where Z0 is the self-impedance of each grounding conductor and Zm is the mutual impedance between adjacent conductors. This configuration is particularly effective in facilities with large ground planes, such as substations or manufacturing plants with heavy machinery.
EMI Reduction in Industrial Environments
Industrial facilities often contain variable-frequency drives (VFDs), arc furnaces, and other nonlinear loads that generate significant harmonic currents. The zigzag grounding system's inherent symmetry provides a low-impedance path for common-mode noise, preventing its propagation through sensitive control circuits. The noise attenuation factor A can be modeled as:
where Zcm is the common-mode impedance and Zdm is the differential-mode impedance of the grounding network.
Practical Implementation Considerations
When deploying zigzag grounding in industrial facilities, several critical factors must be addressed:
- Soil resistivity: High-resistivity soils require deeper electrode burial or chemical treatment to achieve target impedance values.
- Corrosion resistance: Grounding conductors must be selected based on soil pH and moisture content, with copper-clad steel being a common choice.
- Thermal capacity: Conductors must be sized to withstand maximum fault current without exceeding temperature limits defined by IEEE Std 80.
Case Study: Petrochemical Plant Installation
A 2018 implementation at a Gulf Coast refinery demonstrated a 62% reduction in ground potential rise during 40kA fault conditions compared to traditional radial grounding. The system used 12 parallel zigzag conductors spaced at 15-meter intervals, with interconnected copper rods driven to 3-meter depth in treated clay soil.
Harmonic Current Handling
Modern industrial loads generate significant harmonic content, particularly 5th and 7th order harmonics. The zigzag configuration's frequency response shows superior performance above 150Hz compared to star configurations:
where fc is the characteristic frequency of the grounding network, typically between 80-120Hz for industrial installations. This frequency-dependent impedance characteristic helps shunt harmonic currents away from sensitive measurement circuits.
4.2 Integration with Renewable Energy Systems
Zigzag grounding systems are increasingly employed in renewable energy installations to mitigate ground potential rise (GPR) and ensure fault current distribution remains balanced. Unlike conventional solid grounding, zigzag configurations introduce impedance at the neutral point, limiting fault currents while maintaining system stability under asymmetrical conditions.
Grounding Challenges in Renewable Energy Systems
Renewable energy sources such as photovoltaic (PV) arrays and wind farms often operate in distributed configurations with varying fault current contributions. A key challenge arises from the intermittent nature of these sources, which can lead to fluctuating ground return paths. The zigzag grounding transformer provides a controlled impedance path, reducing the risk of transient overvoltages during fault conditions.
where Z0 is the zero-sequence impedance, Zn is the neutral grounding impedance, and Zg represents the grounding grid impedance. This equation highlights how zigzag grounding modifies the zero-sequence network, critical for fault analysis in renewable systems.
Practical Implementation in Solar Farms
In large-scale PV installations, zigzag grounding is often paired with delta-wye transformers to isolate DC and AC grounding systems. A typical configuration involves:
- Neutral grounding resistors (NGRs) to limit fault currents.
- Surge arresters at transformer terminals to suppress transient overvoltages.
- Distributed grounding electrodes to minimize step potential hazards.
Field measurements from a 50 MW solar farm in Arizona demonstrated a 40% reduction in ground fault currents after transitioning from solid grounding to a zigzag configuration, with no adverse impact on inverter synchronization.
Harmonic Mitigation in Wind Turbine Applications
Wind energy systems introduce harmonic distortion due to power electronic converters. The zigzag transformer's inherent filtering properties attenuate triplen harmonics (3rd, 9th, etc.) by providing a low-impedance path for zero-sequence currents:
where Ih is the harmonic current and Vh is the harmonic voltage. Case studies from offshore wind farms show a 28% decrease in harmonic distortion when using zigzag grounding compared to ungrounded systems.
Comparative Analysis with Other Grounding Methods
Grounding Type | Fault Current | Transient Stability | Cost |
---|---|---|---|
Solid Grounding | High | Poor | Low |
Ungrounded | Negligible | Unstable | Medium |
Zigzag Grounding | Controlled | Excellent | High |
The table underscores the trade-offs between fault current magnitude and system stability, with zigzag grounding offering an optimal balance for renewable energy applications.
4.3 Case Studies of Effective Implementations
High-Voltage Substation Grounding in Norway
A 420 kV substation in Norway implemented a zigzag grounding system to mitigate step and touch potentials in rocky terrain with high resistivity (Ï > 3000 Ω·m). The design used a grid depth of 0.5 m with 10 m × 10 m spacing, interconnected with vertical rods at each node. The grounding resistance Rg was derived using Sverak’s formula:
where LT was the total conductor length (1.2 km), A the grid area (10,000 m²), and h the burial depth. The system achieved Rg = 0.8 Ω, well below the IEEE Std 80-2013 limit of 2 Ω.
Telecom Tower Protection in India
A telecom tower in Mumbai employed a zigzag grounding ring to dissipate lightning strikes (peak current > 100 kA). The ring radius was optimized using the electromagnetic transient (EMT) model:
Ks (spacing factor) was set to 0.75 for a 5 m zigzag spacing, reducing Vstep to 650 V during a 10 kA surge—compliant with ITU-T K.56 standards.
Industrial Plant in Germany
A chemical plant in Ludwigshafen integrated zigzag grounding with corrosion-resistant Cu-bonded steel conductors. The system’s frequency-dependent impedance Z(ω) was modeled as:
where L (inductance) and C (capacitance) were minimized using a tight zigzag pitch (2 m). The design suppressed harmonic noise (THD < 1.2%) from variable-frequency drives.
Key Observations
- Terrain adaptation: Zigzag layouts outperform radial designs in high-resistivity soils by 30–40%.
- Transient response: Conductor loops reduce surge impedance by 15% compared to straight grids.
- Maintenance: Periodic soil resistivity testing is critical—cases showed 20% resistance drift over 5 years.
5. Key Research Papers and Articles
5.1 Key Research Papers and Articles
- PDF Practical Grounding/Earthing, Shielding, EMC/EMI and Circuit Board ... — 1.4 Need for standards 5 1.5 EMC - the issues 6 1.6 Electromagnetic disturbances 7 1.7 EMC testing categories 8 1.8 The compatibility gap 9 1.9 Emission, immunity and compatibility 10 1.10 Causes and consequences of EMI 11 1.11 Levels of compliance and EMC engineering application 12 2 EM principles 14 2.1 Introduction 14
- PDF Testing and Evaluation of Grounding Systems: The Revision of the IEEE ... — 9. Measurement of Low-Impedance Grounding Systems by Power System Staged Faults 10. Current Distribution in Extended Grounding Systems 10.1 Introduction 10.2 Test Considerations 10.3 Analysis of Current Distribution in a Grounding System 10.4 Induced Current in the Angled Overhead Ground Wire 10.5 Current Distribution During a Staged Fault Test 11.
- PDF GROUNDS FOR GROUNDING A Circuit-to-System Handbook — 4.7.1. External Signal and Safety Grounding Interconnects 297 between Enclosures 4.7.2. Equipment DC Power, Signal, and Safety Grounding 298 4.7.3. Power Distribution Grounding Schemes in Integrated 301 Clustered Systems 4.7.4. Grounding of Equipment Enclosure Shield 305 4.8. Rack and Cabinet Subsystem Grounding Architecture 308 4.8.1.
- PDF GROUNDING, BONDING - NASA Technical Reports Server (NTRS) — Electrical/electronic Systems Grounding Particulate Pl asma Spacecraft charginq . TABLE OF CONTENTS FORWARD AkSTRACTI KEY WORDS TABLE OF CONTENTS LIST OF ILLUSTRATIONS LIST OF TABLES Page i i iii i v 1.0 SUWY 1 2.0 INTRODUCTION 3 3.0 BACKGROUND 11 ... 4.2.5 Electronic Areas 23 4.2.5.1 Cableway Location 28 4.2.5.2 Power Transformer 3 0
- PDF Analysis of Grounding and Bonding Systems — Grounding and Bonding Systems (CRC Press, 2020). His research interests include the analysis and grounding of power systems, and electrical safety engineering. He is currently the Deputy Editor-in-Chief of the IEEE Transactions on Industry Applications journal. He is active within the Industrial and
- PDF Grounding and Electromagnetic Interference Refresher - IEEE Region 5 — •Electrical Grounding Systems Review •What is EMI -Electromagnetic Interference •The 4 types of EMI and how to spot them ... •Over half of all problems in electrical, electronic and control systems are caused by misunderstanding or a lack of understanding of Earth Ground, Frame Ground, Neutral, Common and Return ...
- Overview of grounding schemes for solidâ€state transformers in ... — Low-resistance grounding is popular in MV systems ranging from 2.4-34.5 kV with the capacitive short circuit fault current larger than 150 A. Distribution systems with low-resistance grounding needs to be shut down to prevent high magnitude fault currents once the fault is identified [49, 58-60]. High-resistance grounding is often used in ...
- PDF DER EG-TOV-TRV White Paper 20220315 - aeso.ca — Recently, effective grounding issue, together with TOV and TRV, have become an escalating concern in many DER or generation projects. 1.1. System Grounding System grounding directly affects TOV and TRV during certain system abnormal situation including short circuit faults.
- Grounding system cost reduction using multiâ€objective optimisation ... — 1 Introduction. The optimisation of the design of grounding grid is an important issue for ensuring safe operation of power system and safety for persons and it is also a key method to decrease electromagnetic interferences which could then cause huge economical loss and social effects [].Many studies related to grounding grid have been published in calculations of grounding system parameters ...
- The Grounded Wye-Delta Transformer with a Zig-Zag Transformer — A most common use of a zig-zag transformer connection is to provide a grounding source for a three-wire delta connected distribution line. When a ground fault occurs on a delta line since there is no ground return path it is impossible to detect that the fault has occurred. In such cases a zig- zag transformer can be connected at the source to provide a path for the ground current to flow back ...
5.2 Industry Standards and Guidelines
- PDF MIL-HDBK-419A Grounding, Bonding, and Shielding for Electronic ... — This document provides basic and application information on grounding, bonding, and shielding practices recommended for electronic equipment.It will provide valuable information and guidance to personnel concerned with the preparation of specifications and the procurement of electrical and electronic equipment for the Defense Communications ...
- PDF Microsoft Word - KSC-STD-E-0022_Change_2_021119TOPDF - NASA — This standard provides design and testing requirements for bonding, grounding, shielding, electromagnetic interference (EMI), lightning protection, electrostatic discharge (ESD) protection, transient protection, and surge suppression for electrical and electronic ground systems (GS) to be used at the Kennedy Space Center (KSC).
- PDF Microsoft PowerPoint - IEEE-IAS_Atlanta_January19_2010.pptx — To Address Issues Related to Large Grounding Systems or Systems in Congested Areas: IEEE Std 81.2-1991 IEEE Guide for Measurement of Impedance and Safety Characteristics of Large, Extended or Interconnected Grounding Systems All of Above Standards were sponsored by:
- PDF IEEE Recommended Practice for Grounding of Industrial and Commercial ... — Obtaining a low-resistance connection to the earth, use of ground rods, connections to water pipes, etc. is discussed. A separate chapter on sensitive electronic equipment is included. Keywords: System grounding, equipment grounding, static and lightning protection grounding, connection to earth, and sensitive electronic equipment grounding.
- PDF Mil-hdbk419a Military Handbook Grounding, Bonding, and Shielding for ... — This handbook emphasizes the necessity for including considerations of grounding, bonding, and shielding in all phases of design, construction, operation, and maintenance of electronic equipment and facilities.
- PDF Microsoft Word - Jacobs final_FAA-STD-019f_ 10-18-2017_.docx — This standard establishes design, procurement, installation, construction, and evaluation standards for lightning protection, transient surge protection, grounding, bonding, shielding configurations and procedures, and control of electrostatic discharge (ESD).
- PDF IEEE Std 142-2007 (Revision of IEEE Std 142-1991) IEEE Recommended ... — As in the case of the zigzag transformer, it can be used for effective grounding or to accomplish resistance-type grounding of an existing ungrounded system. The delta connection must be closed to provide a path for the zero-sequence current, and the delta voltage rating is selected for any standard value.
- PDF Military Standard — This standard addresses the facilities ground systems, as well as grounding, bonding, and shielding and lightning protection for telecommunications C-E facilities and equipments.
- PDF Grounding Requirements for Machinery Instrumentation and Noise Case Studies — 1 Purpose This document describes recommended grounding practices as applicable to Bently Nevada* vibration monitoring systems. It also defines common terms, identifies potential sources of noise, describes basics of a plant grounding system, explains ground loops, and presents a troubleshooting guide to help locate a noise/ground issue and then eliminate it from the system.
- PDF Department of Defense Standard Practice — DEPARTMENT OF DEFENSE STANDARD PRACTICE SHIPBOARD BONDING, GROUNDING, AND OTHER TECHNIQUES FOR ELECTROMAGNETIC COMPATIBILITY, ELECTROMAGNETIC PULSE (EMP) MITIGATION, AND SAFETY
5.3 Recommended Books and Resources
- PDF Practical Grounding/Earthing, Shielding, EMC/EMI and Circuit Board ... — and Circuit Board Layout of Electronic Systems Web Site:www.idc-online.com E-mail: [email protected] . ... expertise and resources to work closely with clients in preparing and presenting ... 5.2 Earth and safety ground 51 5.3 Grounding and frequency 53 5.4 Ground loops 54 5.5 Ground impedance 55 ...
- PDF Practical Earthing of Utility and Industrial Distribution Systems — 3.14 Grounding connections for surge protection equipment 51 3.15 Sensing of ground faults and protection 52 3.16 Supply classifications as per IEE Wiring regulations 53 3.17 More on TN-C-S systems 58 3.18 Installations where use of TN-C-S system is prohibited 59 3.19 Summary 61 4 Ground electrode systems 62 4.1 Introduction 62
- PDF GROUNDS FOR GROUNDING A Circuit-to-System Handbook — 4.7.1. External Signal and Safety Grounding Interconnects 297 between Enclosures 4.7.2. Equipment DC Power, Signal, and Safety Grounding 298 4.7.3. Power Distribution Grounding Schemes in Integrated 301 Clustered Systems 4.7.4. Grounding of Equipment Enclosure Shield 305 4.8. Rack and Cabinet Subsystem Grounding Architecture 308 4.8.1.
- IEEE Recommended Practice for Powering and Grounding Electronic ... — Ask the publishers to restore access to 500,000+ books. An icon used to represent a menu that can be toggled by interacting with this icon. ... IEEE Recommended Practice for Powering and Grounding Electronic Equipment: IEEE Std 1100-1999 ... IEEE Recommended Practice for Powering and Grounding Electronic Equipment: IEEE Std 1100-1999 ...
- Grounds for grounding : a handbook from circuits to systems — GROUNDS FOR GROUNDING Gain a comprehensive understanding of all aspects of grounding theory and application in this new, expanded edition Grounding design and installation are crucial to ensure the safety and performance of any electrical or electronic system irrespective of size. ... edition Grounding design and installation are crucial to ...
- Grounds for Grounding: A Handbook from Circuits to Systems, 2nd Edition — GROUNDS FOR GROUNDING Gain a comprehensive understanding of all aspects of grounding theory and application in this new, expanded edition Grounding design and installation are crucial to ensure the safety and performance of any electrical or electronic system irrespective of size. Successful grounding design requires a thorough familiarity with theory combined with practical experience with ...
- Grounding Books: Learn Grounding Systems | E&S Grounding Solutions — Explore our grounding books & resources. Get expert guidance on design, safety standards & best practices for effective solutions. +1 310.542.8000. Mon - Fri: 9:00AM - 6:00PM. ... This edition introduces a complete electronic book on CD-ROM with over 100 live calculations.
- Grounds for Grounding: A Circuit to System Handbook — GROUNDS FOR GROUNDING. The first book to cover grounding from the circuit to system and across the entire spectrum of applications. Grounds for Grounding provides a complete and thorough approach to the subject of designing electrical and electronic circuits and systems, blending theory and practice to demonstrate how a few basic rules can be applied across a broad range of applications.
- PDF IEEE Std 1100-2005 IEEE (Revision of IEEE Std 1100-1999) Recommended ... — Power Systems Engineering Committee of the Industrial and Commercial Power Systems Department of the IEEE Industry Applications Society Subject: The IEEE Emerald Book® presents a collection of consensus best practices for the powering and grounding of electronic equipment used in commercial and industrial applications. The main objective is to ...
- PDF Zag Grounding Bank Understanding Zig-zag Grounding Banks B John R Boyle ... — of one Zig-Zag grounding bank and/or two grounding banks in parallel to a site specific location. Before addressing the attributes of Zig-Zag grounding banks, it is appropriate to acknowledge that a conventional Wye-Delta transformer (Figure 1) can be used as a grounding bank. However, they are usually not as cost-effective as a zig-zag grounding