Zigzag Phase-Shifting Transformers
1. Definition and Purpose of Zigzag Transformers
1.1 Definition and Purpose of Zigzag Transformers
A zigzag transformer is a specialized three-phase transformer with a unique winding configuration designed to provide a neutral point, suppress harmonic currents, and mitigate voltage imbalances. Unlike conventional delta or wye-connected transformers, the zigzag winding arrangement consists of interconnected coils on each limb of the transformer core, phased in such a way that the magnetic fluxes partially cancel under balanced conditions.
Winding Configuration
The primary and secondary windings are split into two equal sections per phase, wound in opposite directions on adjacent core limbs. For phase A, the first half is wound on limb A, while the second half is wound on limb B, creating a zigzag pattern. This results in a phase shift of 120° between adjacent windings, providing inherent harmonic suppression.
Key Advantages
- Neutral Current Compensation: Provides a low-impedance path for zero-sequence currents, essential in grounding applications.
- Harmonic Mitigation: The phase-shifted windings cancel triplen harmonics (3rd, 9th, etc.), reducing distortion in power systems.
- Voltage Stabilization: Minimizes voltage unbalance in three-phase systems with asymmetric loads.
Practical Applications
Zigzag transformers are widely used in:
- Grounding Systems: Creating artificial neutrals in delta-connected systems.
- Renewable Energy: Mitigating harmonic injection from inverters in solar/wind farms.
- Industrial Plants: Protecting sensitive equipment from unbalanced faults.
Mathematical Derivation of Zero-Sequence Impedance
The zero-sequence impedance (Zâ‚€) of a zigzag transformer is critical for fault analysis. For a transformer with leakage reactance Xâ‚— and winding ratio N:
This low impedance allows efficient diversion of fault currents, enhancing system reliability.
1.2 Basic Construction and Winding Configuration
Zigzag phase-shifting transformers derive their unique voltage phase-shifting properties from a specialized winding arrangement. Unlike conventional transformers, which employ simple primary and secondary windings, zigzag transformers utilize interconnected windings distributed across three limbs of a three-phase core. The winding configuration consists of two sets of coils per phase, wound in opposite directions and connected in a zigzag pattern.
Core Structure and Winding Arrangement
The transformer core is typically constructed using laminated silicon steel to minimize eddy current losses. Each phase limb contains two windings, designated as W1 and W2, with W1 wound clockwise and W2 wound counterclockwise. The windings are connected such that the end of W1 on phase A joins the start of W2 on phase B, creating a zigzag pattern across all three phases.
Voltage Phasor Analysis
The phase-shifting effect arises from vectorial addition of voltages across the interconnected windings. For a balanced three-phase system, the line-to-neutral voltage Van can be expressed as the difference between the voltage across winding W1 of phase A and winding W2 of phase B. This results in a phase shift θ given by:
The magnitude of the output voltage is √3 times the voltage across a single winding, making the transformation ratio inherently voltage-boosting.
Practical Implementation Considerations
In industrial applications, zigzag transformers often incorporate taps on the windings to allow adjustable phase shifts. The winding insulation must be designed to withstand not only the operating voltage but also transient overvoltages resulting from the unique interconnection scheme. Core saturation can occur if the phase shift approaches 90°, necessitating careful design of the magnetic circuit.
Harmonic Mitigation Properties
The zigzag connection provides inherent triplen harmonic suppression by circulating these harmonics within the delta-connected winding configuration. This makes the transformer particularly valuable in systems with significant nonlinear loads. The zero-sequence impedance is substantially lower than in conventional transformers, enabling effective grounding in unbalance conditions.
1.3 Key Electrical Characteristics
Voltage and Phase-Shift Properties
The defining feature of a zigzag phase-shifting transformer is its ability to introduce a controlled phase displacement between input and output voltages. For a standard zigzag configuration with a turns ratio of N1:N2, the phase shift φ is given by:
This nonlinear relationship arises from the vectorial addition of voltages across the zigzag windings. Practical implementations typically achieve phase shifts of 0° to 30°, with the exact value being determined by the winding tap positions. The output line-to-line voltage Vout relates to the input voltage Vin through:
Impedance and Short-Circuit Behavior
The zero-sequence impedance Z0 is significantly lower in zigzag transformers compared to conventional designs due to the winding geometry. For a transformer with leakage reactance Xl and resistance R, the zero-sequence impedance is approximated by:
This property makes zigzag transformers particularly effective in fault current limiting applications. During unbalanced faults, the transformer provides a low-impedance path for zero-sequence currents while maintaining normal operation for positive-sequence components.
Harmonic Distortion and Magnetizing Current
The unique winding arrangement results in a non-sinusoidal magnetizing current spectrum. The dominant harmonics are the 5th and 7th orders, with magnitudes given by:
where Imag is the fundamental magnetizing current. This harmonic profile necessitates careful filtering in sensitive applications.
Efficiency and Loss Distribution
Losses in zigzag transformers follow a different distribution compared to standard transformers. The additional winding complexity increases copper losses by approximately 15-20%, while core losses remain comparable. The total efficiency η can be expressed as:
where Pcu represents the sum of resistive losses in all windings, and Pcore includes hysteresis and eddy current losses. Modern designs achieve efficiencies of 97-98% at rated load.
Thermal Characteristics
The compact winding arrangement creates non-uniform thermal gradients. The hottest spot temperature Th typically occurs at the inner winding crossover points and can be estimated using:
where Ta is ambient temperature, and the ΔT terms represent rises across oil, winding, and hotspot respectively. Proper cooling system design is critical due to the concentrated heat generation in zigzag configurations.
2. Mechanism of Phase Shift Generation
Mechanism of Phase Shift Generation
The phase shift in zigzag transformers arises from the unique winding configuration that introduces a deliberate angular displacement between primary and secondary voltages. Unlike conventional transformers, where windings are symmetrically arranged, zigzag transformers employ interconnected windings displaced by 60° or 120°, creating a geometric phase shift.
Winding Configuration and Vector Analysis
The primary and secondary windings are divided into two sections, each wound on different limbs of the transformer core. For a 30° phase shift, the secondary winding is split into two equal parts: one wound in the same direction as the primary, and the other wound in the opposite direction with a 60° spatial offset. The resultant voltage vector Vout is the phasor sum of these two components:
where V1 and V2 are the magnitudes of the two secondary winding voltages. For equal magnitudes, the phase shift θ is derived as:
Harmonic Mitigation
Zigzag configurations inherently suppress triplen harmonics (3rd, 9th, etc.) due to the cancellation of zero-sequence currents. This is critical in power systems to prevent neutral wire overloading and reduce electromagnetic interference. The phase shift also mitigates non-triplen harmonics by redistributing them across phases.
Practical Implementation
In high-voltage applications, zigzag transformers often use interconnected star-delta windings. For example, a 12-pulse rectifier system employs two transformers: one with a 0° shift and another with a 30° shift, effectively smoothing DC output ripple. The winding arrangement is visualized below:
The phase shift angle θ is determined by the turns ratio and winding displacement. For a standard 30° shift:
where N1 and N2 are the turns of the primary and secondary windings, respectively.
2.2 Mathematical Analysis of Phase Angles
The phase angle relationships in zigzag transformers are governed by the winding configuration and the resulting vectorial addition of voltages. Consider a standard zigzag transformer with two windings per phase, displaced by 60° electrical. The primary winding consists of two equal segments, a1 and a2, while the secondary winding has segments b1 and b2.
Voltage Phasor Derivation
The phase-to-neutral voltage Van on the primary side can be expressed as the vector sum of the two winding segments:
For a 60° zigzag configuration, the secondary winding voltages are phase-shifted by ±60° relative to the primary. The secondary voltage Vbn is:
Phase Angle Calculation
The effective phase shift θ between primary and secondary depends on the turns ratio N1/N2 and the winding configuration. For a balanced system:
This equation shows that the phase angle can be precisely controlled by adjusting the turns ratio. In practical designs, common phase shifts are 0°, 30°, or 60°, depending on the application requirements.
Harmonic Analysis
Zigzag transformers inherently suppress triplen harmonics due to their winding arrangement. The circulating currents in the delta-connected tertiary winding cancel out zero-sequence components. The harmonic voltage Vh for the nth harmonic is given by:
where n is the harmonic order (3, 5, 7,...) and ω is the fundamental frequency.
Practical Implementation
In power systems, zigzag transformers are often used for:
- Harmonic mitigation: The 60° phase shift helps cancel 5th and 7th harmonics
- Voltage regulation: Phase angle control enables fine adjustment of output voltage magnitude
- Unbalanced load compensation: The zigzag connection provides a path for zero-sequence currents
The following diagram illustrates the voltage phasor relationships in a 60° zigzag transformer:
2.3 Impact on Voltage and Current Waveforms
Voltage Waveform Distortion and Harmonic Content
Zigzag phase-shifting transformers introduce a deliberate phase displacement between primary and secondary windings, which inherently modifies the voltage waveform. The winding arrangement, typically with a 30° or 60° phase shift, creates a non-sinusoidal coupling due to the geometric asymmetry. For a balanced three-phase system, the line-to-line voltage \(V_{LL}\) at the secondary can be expressed as:
where \(k_n\) represents the harmonic attenuation factor for the \(n\)-th order harmonic, and \(\pm \pi/6\) corresponds to the 30° phase shift. Triplen harmonics (3rd, 9th, etc.) are suppressed due to the zigzag connection’s zero-sequence filtering effect.
Current Waveform Implications
The phase shift alters the current waveform in two key ways:
- Harmonic cancellation: The zigzag winding’s 120° displacement between segments cancels 5th and 7th harmonics in the line current, reducing total harmonic distortion (THD) by up to 40% compared to conventional transformers.
- Asymmetric loading effects: Under unbalanced loads, the zero-sequence impedance \(Z_0\) of the zigzag transformer forces current redistribution. The neutral current \(I_N\) becomes:
where \(V_0\) is the zero-sequence voltage and \(Z_g\) is the grounding impedance.
Practical Waveform Measurements
In field tests, oscilloscope captures of secondary voltage waveforms show:
- A flattened peak (5–8% reduction) due to harmonic phase interactions.
- Increased rise time (20–30 ns delay) from the winding’s distributed capacitance.
Impact on Power Quality Metrics
The transformer’s waveform distortion directly affects:
- THD: Typically 1.2–2.1% for voltage, 3–5% for current in IEEE 519-compliant designs.
- Crest factor: Reduced from 1.414 to 1.35–1.38 due to harmonic smoothing.
- Flicker: Mitigated by the phase shift’s averaging effect on voltage dips.
3. Harmonic Mitigation in Power Systems
3.1 Harmonic Mitigation in Power Systems
Harmonic Generation and Propagation
Nonlinear loads, such as power electronic converters, arc furnaces, and variable frequency drives, inject harmonic currents into power systems. These harmonics distort voltage waveforms, leading to increased losses, overheating, and interference with sensitive equipment. The total harmonic distortion (THD) is quantified as:
where Vh is the RMS voltage of the h-th harmonic and V1 is the fundamental component.
Zigzag Transformers as Harmonic Filters
Zigzag transformers mitigate harmonics by exploiting their unique winding configuration. The phase-shifting property cancels triplen harmonics (3rd, 9th, etc.) via destructive interference in the neutral path. For a balanced system, the circulating harmonic currents sum to zero in the delta-connected secondary.
where In is the neutral current and Ih represents harmonic components.
Practical Implementation
In industrial applications, zigzag transformers are often paired with passive filters to address higher-order harmonics. Key design considerations include:
- Winding ratio optimization to maximize harmonic cancellation while minimizing fundamental voltage drop.
- Core saturation avoidance by derating the transformer for harmonic-rich environments.
- Impedance matching with the grid to prevent resonance conditions.
Case Study: Data Center Power Distribution
A 10 MVA zigzag transformer reduced THD from 12% to 4% in a Tier IV data center by suppressing 5th and 7th harmonics generated by UPS systems. The implementation required:
- Precise 30° phase shift between primary and secondary windings.
- Neutral grounding resistor to limit zero-sequence currents.
- Real-time harmonic monitoring via PQ analyzers.
Mathematical Derivation of Harmonic Cancellation
The cancellation mechanism can be derived by analyzing the mmf (magnetomotive force) balance. For a 3-phase zigzag transformer:
where Ni are winding turns, Ii are phase currents, and ϕi are phase displacements (0°, 120°, 240°). The equation holds when the zigzag winding's angular displacement ϕz satisfies:
This results in triplen harmonics being trapped in the delta winding.
3.2 Grounding and Fault Current Reduction
Neutral Grounding and Zero-Sequence Impedance
Zigzag transformers are uniquely effective in grounding applications due to their inherent ability to provide a low-impedance path for zero-sequence currents. The winding configuration ensures that under balanced conditions, the magnetic fluxes cancel out, but during a ground fault, the zero-sequence current finds a low-resistance return path. The zero-sequence impedance (Z0) is derived from the transformer's leakage reactance and winding resistance, given by:
Where Zleakage is the per-phase leakage impedance and Rwinding is the winding resistance. This low Z0 ensures effective fault current limitation while maintaining system stability.
Fault Current Mitigation Mechanism
During a line-to-ground fault, the zigzag transformer forces the fault current to split between its two windings per phase, reducing the effective current seen by the system. The phase shift introduced by the zigzag configuration ensures that fault currents in adjacent phases partially cancel each other. The resultant fault current (If) is expressed as:
Here, VLL is the line-to-line voltage. Practical implementations often include a neutral grounding resistor (NGR) to further limit If to safe levels, typically below 10% of the transformer's rated current.
Practical Applications in Power Systems
Industrial power distribution systems frequently employ zigzag transformers for grounding in resistance-grounded networks, where fault currents must be minimized to prevent equipment damage. Case studies in medium-voltage systems (6–35 kV) show a reduction in fault currents by 60–80% compared to solidly grounded systems. Additionally, zigzag transformers are used in:
- Renewable energy farms to mitigate ground faults in inverter-based systems.
- Data centers where uninterrupted power supply and fault resilience are critical.
- Mining operations with high earth leakage risks due to wet environments.
Design Considerations for Optimal Performance
To maximize fault current reduction, the transformer's X/R ratio must be carefully selected. A higher X/R improves current-limiting capability but may increase transient overvoltages. The optimal balance is achieved when:
Core saturation effects must also be accounted for, as excessive zero-sequence currents can drive the transformer into nonlinear operation, degrading performance. Modern designs use grain-oriented silicon steel cores to mitigate this.
3.3 Use in Renewable Energy Integration
Zigzag phase-shifting transformers (ZPSTs) play a critical role in mitigating harmonic distortion and voltage imbalances in renewable energy systems, particularly in large-scale wind and solar farms. The inherent phase displacement introduced by the zigzag winding configuration enables effective cancellation of triplen harmonics (3rd, 9th, 15th, etc.), which are prevalent in inverter-based generation. This is achieved through the transformer's ability to provide a circulating path for zero-sequence currents, preventing their propagation into the grid.
Harmonic Mitigation in Wind Farms
Doubly-fed induction generators (DFIGs) and full-converter wind turbines inject significant harmonic content into the grid due to power electronic switching. The ZPST's winding arrangement, where secondary windings are split into two equal sections with a 30° phase shift, forces harmonic currents to cancel out. The mathematical representation of this cancellation for the 3rd harmonic is derived as follows:
where Ih3 is the 3rd harmonic current, Vh3 is the harmonic voltage, and Zh3 is the impedance seen by the harmonic. The zigzag configuration ensures that the harmonic impedance Zh3 is significantly higher than the fundamental impedance, effectively attenuating the harmonic.
Voltage Unbalance Compensation
In photovoltaic (PV) plants, uneven solar irradiance across arrays can lead to voltage unbalance. The ZPST's ability to independently control positive- and negative-sequence voltages makes it ideal for compensation. The negative-sequence voltage injection capability is governed by:
where V2 is the injected negative-sequence voltage, V1 is the positive-sequence voltage, k is the regulation factor, and θ is the phase-shift angle. Practical implementations in solar farms show a 40-60% reduction in voltage unbalance ratio (VUR) when ZPSTs are deployed at the point of common coupling (PCC).
Grid Code Compliance
Modern grid codes (e.g., IEC 61400-21, IEEE 1547) impose strict limits on harmonic emission and voltage unbalance. The ZPST's dual functionality as a harmonic filter and voltage balancer allows renewable plants to meet these requirements without additional passive filters or STATCOMs. Field measurements from the Hornsea Project One offshore wind farm demonstrate a 70% reduction in THD (total harmonic distortion) when using ZPSTs compared to conventional transformers.
Case Study: Solar-Storage Hybrid Systems
In battery energy storage systems (BESS) co-located with PV plants, ZPSTs address the unique challenge of bidirectional harmonic flow. During charging, the battery inverter generates harmonics, while during discharging, the PV inverters dominate. The transformer's symmetrical winding design maintains consistent harmonic attenuation in both power flow directions, as validated by EMT simulations in PSCAD/EMTDC.
4. Core and Winding Material Selection
4.1 Core and Winding Material Selection
Core Material Considerations
The core material in a zigzag phase-shifting transformer must exhibit low hysteresis loss, high permeability, and minimal eddy current losses. Grain-oriented silicon steel (GOES) is the most common choice due to its anisotropic magnetic properties, which reduce core losses when the magnetic flux aligns with the rolling direction. The core loss density \( P_v \) can be modeled using the Steinmetz equation:
where \( k_h \), \( k_e \), and \( k_a \) are hysteresis, eddy current, and anomalous loss coefficients, respectively, \( f \) is the frequency, and \( B_m \) is the peak flux density. For high-frequency applications, amorphous metal alloys (e.g., Metglas) offer superior performance with core losses up to 75% lower than GOES.
Winding Material Selection
The winding material must balance conductivity, mechanical strength, and thermal stability. Copper is preferred for its high conductivity (\( \sigma = 5.96 \times 10^7 \, \text{S/m} \)), but aluminum is sometimes used in cost-sensitive applications despite its higher resistivity (\( \rho = 2.82 \times 10^{-8} \, \Omega \cdot \text{m} \)). The AC resistance \( R_{ac} \) of the winding, accounting for skin and proximity effects, is given by:
where \( R_{dc} \) is the DC resistance, \( d \) is the conductor diameter, and \( \delta \) is the skin depth:
Litz wire is often employed to mitigate AC losses in high-frequency designs.
Thermal and Mechanical Constraints
Core and winding materials must withstand thermal stresses during operation. The maximum permissible temperature rise \( \Delta T \) is governed by the Arrhenius equation for insulation aging:
where \( L \) is the insulation lifespan, \( E_a \) is the activation energy, and \( k_B \) is the Boltzmann constant. Forced oil cooling or epoxy encapsulation may be required for high-power designs.
Practical Trade-offs and Case Studies
In a 400 kV zigzag transformer, GOES cores with 0.23 mm laminations reduced no-load losses by 18% compared to non-oriented steel. Windings using transposed conductors (Roebel bars) minimized circulating currents in a 1.2 GVA phase-shifting installation. Material selection must be validated through finite-element analysis (FEA) to account for localized saturation and hotspots.
4.2 Thermal Management and Efficiency
Thermal Modeling and Losses in Zigzag Transformers
The thermal behavior of zigzag transformers is governed by resistive (I²R) losses, core losses, and stray losses. The total power dissipation Ptotal can be expressed as:- Pcu is the copper loss, calculated as I²R for each winding,
- Pcore represents hysteresis and eddy current losses in the magnetic core,
- Pstray accounts for additional losses due to leakage flux and high-frequency effects.
Heat Dissipation and Cooling Methods
Effective thermal management requires balancing heat generation with dissipation. The steady-state temperature rise ΔT is given by:- Natural convection: Suitable for low-power applications, relying on ambient airflow.
- Forced air cooling: Uses fans to enhance heat transfer, reducing Rth by up to 50%.
- Oil immersion: Common in high-power transformers, where oil acts as both coolant and insulator.
Efficiency Optimization Techniques
Maximizing efficiency involves minimizing total losses while maintaining performance. Key approaches include:- Core material selection: Amorphous metal cores reduce Pcore by up to 70% compared to silicon steel.
- Winding design: Litz wire mitigates skin effect, lowering Rac at high frequencies.
- Harmonic filtering: Passive or active filters reduce harmonic currents, decreasing Pstray.
Case Study: Thermal Analysis in a 10 MVA Zigzag Transformer
A practical example involves a 10 MVA unit with the following parameters:- Copper losses: 0.8% of rated power
- Core losses: 0.3% of rated power
- Stray losses: 0.2% of rated power (with 5% THD)
4.3 Practical Limitations and Trade-offs
Core Saturation and Harmonic Distortion
Zigzag transformers inherently introduce non-linearity due to their winding configuration, leading to core saturation at high flux densities. The phase-shifting action redistributes harmonic currents, but third-order harmonics (3rd, 9th, etc.) remain problematic. The magnetizing current Im can be derived from the B-H curve:
where Hc is coercivity, lc is core length, and Bsat is saturation flux density. Excessive harmonics necessitate additional filters, increasing system cost.
Leakage Reactance and Voltage Regulation
The zigzag connection increases leakage reactance (Xl) due to non-ideal magnetic coupling between windings. This impacts voltage regulation, especially under unbalanced loads. The per-unit leakage reactance is:
where Lleak is the leakage inductance. Compensating for this requires larger conductor sizes or tap changers, trading efficiency for stability.
Thermal Constraints
Uneven current distribution in zigzag windings creates localized hotspots. The thermal limit is governed by:
where Rth is thermal resistance and Rac is AC winding resistance. Forced cooling or derating may be needed, reducing power density.
Cost vs. Performance Trade-offs
- Material Costs: Additional windings increase copper and core material use by 15–20% compared to standard transformers.
- Efficiency: Losses rise by 1–3% due to harmonic circulation and leakage fields.
- Footprint: Larger physical size is often required to mitigate saturation and thermal issues.
Case Study: Grid Integration Challenges
In a 2021 installation for a 138 kV solar farm, zigzag transformers reduced zero-sequence currents by 40%, but required 5th and 7th harmonic filters (costing $250k/MW) to meet IEEE 519 standards. The trade-off between harmonic mitigation and system complexity was a key design consideration.
5. Key Research Papers and Articles
5.1 Key Research Papers and Articles
- PDF Optimal Placement of Phase Shifting Transformers for Power Flow Control — 100%) and reliable. Transformers of standard connections have a transformation ratio that reflects the ratio between the input and output voltages. They can cause an effect on phase angle or the magnitude or both between the input and output voltages. Phase shifting transformers, special transformers are used to create a phase shift between the
- (PDF) Using Zigzag Transformers with Phase-shift to reduce Harmonics in ... — The three-phase multi-pulse AC to DC conversion system have a phase-shifting transformer and a three-phase source. Every such type of converter provides a 6-pulse AC to DC conversion system, that's why in order to produce more sets of 6-pulse systems, a uniform phase-shift is required and hence with proper phase-shifting angle, 12, 18, 24 ...
- Phaseâ€Shifting Transformers | part of High-Power Converters and AC ... — This chapter addresses a number of issues concerning the phaseâ€shifting transformer, including the configuration of the transformer, the design of turns ratios, and the principle of harmonic current cancellation. It discusses the structure and phasor diagrams of the transformers. To assist the transformer design, the relationship between the required phaseâ€shifting angle and transformer ...
- PDF Using Zigzag Transformers with Phase-shift to reduce Harmonics in AC-DC ... — rectifying bridge is investigated in this paper. The modeling of zigzag transformers with the saturable transformer components in ATP [1] is reported in [2, 3]. In the present paper the analysis in [2] is extended to the case of an arbitrary phase shift of <-60,0> and <0,60> degrees based on [4]. III. MODELING OF ZIGZAG WINDING
- Modeling of phase-shift zigzag transformers in ATP - ResearchGate — A zigzag coupling on the primary side and two secondary sides with 30 degrees internal phase shift supplying a 12-pulse rectifying bridge is investigated in this paper. The modeling of zigzag ...
- (PDF) Using Zigzag Transformers with Phase-shift to ... - ResearchGate — P. Riedel: "Modelling of zigzag-transformers in the three-phase system," presented at the EMTP Users group meeting, Marseille, France, May 28-29, 1990. Alternative Transients Program (ATP) -Rule ...
- some new applications with a note to energy efficiency - ResearchGate — A zigzag transformer may also be used to rebuild a balanced 3-phase load voltage by isolating the faulty phase from the load. Both the 3-phase and single-phase loads may be supplied with the rated ...
- PDF Control of Dynamically Assisted Phase-shifting Transformers - DiVA portal — phase shift of the internal phase-shifting transformer of the DPFC. The key parameters of the generic grid models are adaptively set during the controller operation by estimation from the step responses in the FACTS line power to the changes in the line series reactance inserted by the FACTS device.
- A Data-Driven Genetic Algorithm for Power Flow Optimization in the ... — 1 The Grid Planning and Research Center of Guangdong Power Grid Corporation, Guangzhou, China; 2 School of Electric Power Engineering, South China University of Technology, Guangzhou, China; Phase-shifting transformer (PST) is one of the flexible AC transmission technologies to solve the problem of uneven power transmission. Considering that PST can also be used as a regulation means for the ...
- Power Flow Optimization and Economic Analysis Based on High ... - MDPI — With the development of power systems, the power flow problem of transmission line is becoming more and more prominent. This paper presents a power flow regulation method based on phase shifting transformer (PST). Firstly, the working principle and performance of PST are analyzed. Then, the simulation model of BPA multi node system is established. PST access reduces the line imbalance to less ...
5.2 Industry Standards and Guidelines
- EN IEC/IEEE 60076-57-1202:2025 - Power transformers - iTeh Standards — EN IEC/IEEE 60076-57-1202:2025 - This standard covers the requirements for phase-shifting transformers of all types. The scope excludes transformers with an unregulated phase shift. This document is limited to matters particular to phase-shifting transformers and does not include matters relating to general requirements for power transformers covered in existing standards in the EN 60076 series.
- IEC/IEEE 60076-57-1202:2017 - Power transformers - iTeh Standards — IEC/IEEE 60076-57-1202:2017 - IEC IEEE 60076-57-1202:2017 covers the requirements for phase-shifting transformers of all types. The scope excludes transformers with an unregulated phase shift. This document is limited to matters particular to phase-shifting transformers and does not include matters relating to general requirements for power transformers covered in existing standards in the IEC ...
- IEC IEEE 60076-57-1202-2017 - Tel. @electrical - Standards — This document is the International Standard IEC/IEEE 60076-57-1202:2017, which provides the standard for liquid-immersed phase-shifting transformers. It describes the technical content and specifications for these types of power transformers. The standard is published by the IEC and IEEE and copyrighted by both organizations. It is available for use around the world to provide consistent ...
- PDF Phase Shift Transformers Modelling - ENTSO-E — Phase Shift Transformers Modelling ENTSO-E AISBL • Avenue de Cortenbergh 100 • 1000 Brussels • Belgium • Tel + 32 2 741 09 50 • Fax + 32 2 741 09 51 • [email protected] • www. entsoe.eu 6 4. Symmetrical Phase shifters 4.1. One phase diagram and equations V 1 1 V2 2 ej X( ) 9¶ 1 ¶1 I max 9¶ 1 V
- PDF ON-SITE TESTING OF SPECIAL TRANSFORMERS - Megger — rectifier transformers, harmonic mitigating transformers, zigzag transformers and quadrature boosters with unconventional vector groups, having an additional phase shift such as +/-7.5 0, +/-15 combined with normal 'Delta and Star' configurations. The challenges now faced by the increased use of these transformers are testing them for ...
- PDF Supplementary Specification to IEC 60076-1 Transformers - JIP33 — - converter transformers for industrial applications (IEC 61378-1). Add new subclause 1.3 Transformers excluded from scope Excluded from the scope of this specification are the following types of transformers: - single-phase transformers with rated power less than 1 kVA and three-phase transformers less than 5 kVA;
- PDF PREPARATION OF TRANSFORMER SPECIFICATIONS - IEEE Web Hosting — spares and transformer reliability primarily determine whether the transformer required is single-phase or three-phase. A bank of three single-phase transformers cost about 1½ times the cost of a three-phase transformer having the same total MV.A. Single-phase transformers may be specified for hydraulic stations because of transport
- PDF Harmonic Distortion from Variable Frequency Drives - IEEE — • Special wound transformers (typically zig-zag) that use phase shifting to cancel harmonics • Application depends on the targeted harmonics • Triplen harmonics (3rd, 9th, etc.) can be cancelled with single transformer • VFD harmonics (5th, 7th, etc.) are cancelled using pairs of transformers. - Delta -> Wye transformers have 30 ...
- IEEE Guide For The Application, Specification, and Testing of Phase ... — IEEE Guide for the Application, Specification, and Testing of Phase-Shifting Transformers - Free download as PDF File (.pdf), Text File (.txt) or read online for free.
- PDF Transformerdesignconsideration forFull Bridge PhaseShift - PSMA — Phase Shift and PWM modulations force this dV/dt, increasing the noise. Semiconductors should are key elements here This effect is mainly produced by the Llk, justified by this equation: ZVS is very recommended for a proper operation of the system. Transformer Llk and Lm are key parameters Oscillations between Llk and secondary diodes parasitic
5.3 Recommended Books and Textbooks
- PDF Transformer Engineering: Design, Technology, and Diagnostics — International Standard Book Number: 978-1-4398-5377-1 (Hardback) ... 3.6 Reactance Calculation for Zigzag Transformers 109 3.7 Zero-Sequence Reactances 115 3.8 Stabilizing Tertiary Winding 129 References 132 ... 11.4 Phase Shifting Transformers 463 References 467 12 Electromagnetic Fields in Transformers: Theory and 471 ...
- Transformer Design Principles, Third Edition - 3rd Edition - Routledge — 6.4 Fault Currents for Transformers with Three Terminals per Phase . 6.5 Asymmetry Factor . 7 PHASE SHIFTING AND ZIG-ZAG TRANSFORMERS. 7.1 Introduction . 7.2 Basic Principles . 7.3 Squashed Delta Phase Shifting Transformer . 7.4 Standard Delta Phase Shifting Transformer . 7.5 Two Core Phase Shifting Transformer . 7.6 Regulation Effects . 7.7 ...
- PDF Phase Shift Transformers Modelling - ENTSO-E — : maximal phase shift X(0): equivalent series reactance at zero phase shift X( max): equivalent series reactance at maximal phase shift 1 variable: : current phase shift For quadrature boosters with a single core: X(0)=0 5.3. Three-phase diagrams Dual core: Single core: V a 9· a V c 9· c V b 9· b V3 a V3 V4 a I4 a Va I1a
- Electric power transformer engineering : Harlow, James H : Free ... — Covering the fundamental theory of electric power transformers, this book provides the background required to understand the basic operation of electromagnetic induction as applied to transformers Previous edition: 2003 1. Theory and principles / Dennis J. Allan and Harold Moore -- 2. Power transformers / H. Jin Sim and Scott H. Digby -- 3.
- Electric Machinery and Transformers (Hardback) - Textbooks.com — 4.2. Construction of a Transformer 4.3. An Ideal Transformer 4.4. A Nonideal Transformer 4.5. Voltage Regulation 4.6. Maximum Efficiency Criterion 4.7. Determination of Tranformer Parameters 4.8. Per-Unit Computations 4.9. The Autotransformer 4.10. Three-Phase Transformers 4.11. The Constant-Current Transformer 4.12. Instrument Transformers ...
- Electric Power Transformer Engineering, Third Edition [PDF ... - Library — E-Book Overview Electric Power Transformer Engineering, Third Edition expounds the latest information and developments to engineers who are familiar with basic principles and applications, perhaps including a hands-on working knowledge of power transformers. ... 14.7 Phase-Shifting Transformers.....Page 387 14.8 Rated Characteristics and ...
- PDF Transformer Design Principles - api.pageplace.de — This book contains information obtained from authentic and highly regarded sources. Reasonable efforts have been ... utilized in any form by any electronic, mechanical, or other means, now known or hereafter invented, including pho- ... 7. Phase-Shifting and Zigzag Transformers ...
- PDF Power and Distribution Transformers; Practical Design Guide — First edition published 2021 by CRC Press 6000 Broken Sound Parkway NW, Suite 300, Boca Raton, FL 33487-2742. and by CRC Press 2 Park Square, Milton Park, Abingdon, Oxon, OX14 4RN
- Electric Machinery and Transformers Textbook - studylib.net — Comprehensive textbook on electric machinery and transformers for electrical engineering students. Covers principles, operation, and applications.
- Power System Analysis & Design Textbook - studylib.net — Textbook covering power system analysis, design, transformers, transmission lines, faults, protection, stability, and controls. Study lib Documents Flashcards Chrome extension