Zigzag Transformer Configurations
1. Definition and Purpose of Zigzag Transformers
Definition and Purpose of Zigzag Transformers
Fundamental Structure
A zigzag transformer is a specialized three-phase transformer with a unique winding configuration where each phase winding is split into two equal halves, connected in opposite polarity across different magnetic cores. Unlike conventional delta or wye connections, the zigzag arrangement provides inherent harmonic suppression and neutral stabilization.
The primary winding consists of six coils per phase (two per limb), with each pair wound in opposite directions. This creates a phase displacement of 120° between voltage vectors, mathematically expressed as:
Key Operational Principles
Zigzag transformers exhibit three critical characteristics:
- Zero-sequence impedance: Provides low-impedance path for triplen harmonics (3rd, 9th, 15th...) while blocking positive/negative sequence currents
- Neutral current compensation: The opposing winding halves cancel zero-sequence fluxes, enabling unbalanced load handling
- Voltage distortion mitigation: The 30° phase shift between primary and secondary suppresses 5th and 7th harmonics
The zero-sequence impedance (Z0) can be derived from the transformer's leakage reactance (XL) and winding resistance (R):
Practical Applications
Zigzag configurations are predominantly used in:
- Grounding systems: Creating artificial neutrals in ungrounded delta systems (common in industrial power distribution)
- Harmonic filtering: Serving as low-cost passive filters in variable frequency drive applications
- Fault current limitation: Reducing arc flash risks in medium-voltage switchgear
In renewable energy systems, zigzag transformers enable asymmetrical fault ride-through by providing a controlled path for ground currents during single-line-to-ground faults. The winding arrangement forces zero-sequence currents to circulate internally rather than propagating through the network.
Comparative Advantages
When benchmarked against traditional grounding transformers:
- 30-40% smaller footprint than equivalent delta-wye units for the same kVA rating
- 60% reduction in triplen harmonics compared to ungrounded systems
- Faster transient response (typically < 1 cycle) for ground fault detection
The voltage regulation capability stems from the transformer's ability to maintain balanced phase voltages under unbalanced loading conditions. This is quantified by the voltage unbalance factor (VUF):
where V0 is zero-sequence voltage and V1 is positive-sequence voltage.
1.2 Core Principles and Operating Mechanism
Magnetic Flux Distribution and Phase Shift
The zigzag transformer derives its unique properties from the deliberate asymmetry in its winding arrangement. Unlike conventional transformers, where windings are symmetrically distributed across limbs, the zigzag configuration employs interleaved windings that introduce a controlled phase displacement. Each limb of the core contains two windings from different phases, wound in opposite directions. This arrangement ensures that the magnetic flux generated by one phase partially cancels the flux from another, resulting in a net flux that is phase-shifted by 30° in a standard configuration.
Here, φnet represents the net flux, while φA, φB, and φC denote the individual phase fluxes. The subtraction and addition arise from the opposing winding polarities.
Zero-Sequence Current Suppression
A key advantage of the zigzag transformer is its ability to block zero-sequence currents, which are often responsible for ground faults in three-phase systems. The winding configuration ensures that zero-sequence currents produce opposing magnetomotive forces (MMF), effectively canceling them out. The zero-sequence impedance (Z0) is given by:
where Zn is the neutral grounding impedance and Zleakage is the transformer's leakage impedance. This property makes zigzag transformers particularly useful in grounding applications where fault current limitation is critical.
Voltage Regulation and Harmonic Mitigation
Due to their inherent phase-shifting capability, zigzag transformers are effective in mitigating triplen harmonics (3rd, 9th, etc.). The harmonic currents circulate within the delta-connected secondary, preventing their propagation into the grid. The voltage regulation is governed by:
Here, N1 and N2 are the primary and secondary turns, respectively, while θ is the phase shift angle (typically 30°).
Practical Applications in Power Systems
Grounding Transformers: Zigzag configurations are widely used to provide a neutral point in ungrounded or delta-connected systems, enabling effective fault detection and isolation.
Harmonic Filtering: In industrial settings with non-linear loads, zigzag transformers suppress harmonic distortion by providing a low-impedance path for zero-sequence currents.
Phase Balancing: In unbalanced loads, the transformer redistributes phase currents, improving system stability.
1.3 Comparison with Standard Transformer Configurations
Core Structural Differences
Zigzag transformers differ fundamentally from standard delta-wye or delta-delta configurations in their winding arrangement. While conventional transformers use symmetrical phase-shifted windings, the zigzag configuration employs interconnected windings across different phases. This results in a unique voltage phasor diagram where each winding contributes to both phase and neutral voltage regulation. The zero-sequence impedance of a zigzag transformer is significantly lower than that of a delta-wye transformer, making it particularly effective in unbalanced load conditions.
Harmonic Mitigation Capabilities
Standard transformers exhibit limited inherent harmonic suppression, often requiring external filters. In contrast, the zigzag configuration's winding arrangement creates a natural path for triplen harmonics (3rd, 9th, 15th...) to circulate within the delta-connected tertiary winding. This characteristic is quantified by the harmonic suppression factor Hs:
where Z0 is the zero-sequence impedance and Z1 is the positive-sequence impedance.
Neutral Current Handling
Unlike standard wye-connected transformers that require oversized neutral conductors for unbalanced loads, zigzag configurations inherently redistribute neutral currents through phase windings. The neutral current In splits equally between two windings in each phase:
This allows zigzag transformers to handle up to 300% neutral current without derating, compared to the 173% limit in conventional wye systems.
Voltage Regulation Performance
Under unbalanced load conditions, standard transformers exhibit voltage asymmetry that follows the sequence component relationship:
Zigzag transformers demonstrate superior voltage regulation due to their negative-sequence impedance Z2 being nearly equal to positive-sequence impedance Z1, unlike delta-wye transformers where Z2 ≈ 0.85Z1.
Practical Implementation Trade-offs
- Core Utilization: Zigzag configurations require 15-20% more core material than equivalent delta-wye transformers due to non-optimal winding utilization
- Efficiency: Full-load efficiency is typically 0.5-1.5% lower than standard configurations due to additional I²R losses in the interconnected windings
- Fault Current Contribution: Provide 40-60% lower fault current contribution compared to delta-wye transformers during line-to-ground faults
Case Study: Industrial Power System Retrofit
A 13.8kV manufacturing plant replaced delta-wye transformers with zigzag units to address persistent neutral overcurrent issues. Measurements showed:
Parameter | Delta-Wye | Zigzag |
---|---|---|
3rd Harmonic Distortion | 12.7% | 3.2% |
Neutral Current (unbalanced) | 187% rated | 112% rated |
Voltage Unbalance Factor | 2.8% | 0.9% |
2. Voltage and Current Relationships
2.1 Voltage and Current Relationships
In a zigzag transformer, the voltage and current relationships are governed by the unique winding arrangement where each phase consists of two equal windings displaced by 120° on the magnetic core. The primary and secondary windings are interconnected in a zigzag pattern, resulting in specific phase shifts and magnitude transformations.
Voltage Transformation
The line-to-neutral voltage VLN on the secondary side is derived from the vector sum of two winding voltages. For a balanced three-phase system, the transformation ratio is given by:
where VLL is the line-to-line voltage, N1 is the number of primary turns per phase, and N2 is the number of secondary turns per winding segment. The √3 factor arises from the 120° phase displacement between windings.
Current Relationships
The primary and secondary currents in a zigzag transformer follow an inverse relationship with the turns ratio, but with an additional √3 factor due to the winding geometry:
Here, I1 is the primary current, and I2 is the secondary line current. The zigzag connection inherently provides a 30° phase shift between primary and secondary currents, which is crucial for harmonic mitigation in power systems.
Zero-Sequence Characteristics
Zigzag transformers exhibit unique zero-sequence impedance properties. The zero-sequence current I0 flows through the interconnected windings, creating a cancellation effect:
where Z0 is the zero-sequence impedance and Z1 is the positive-sequence impedance. This makes zigzag transformers particularly effective in grounding applications to limit fault currents.
Practical Implications
In industrial power systems, zigzag transformers are often used for:
- Harmonic filtering: The 30° phase shift helps cancel 3rd-order harmonics.
- Grounding: Provides a low-impedance path for zero-sequence currents during faults.
- Voltage stabilization: Mitigates voltage unbalance in three-phase systems.
The following diagram illustrates the winding connections and phasor relationships:
2.2 Harmonics Mitigation Capabilities
Phase-Shift Cancellation of Triplen Harmonics
Zigzag transformers inherently suppress triplen harmonics (3n-order harmonics, where n is an integer) through phase displacement. The 120° phase shift between adjacent windings causes triplen harmonic currents to sum to zero in the neutral connection. For a balanced system, the neutral current In for the k-th harmonic is:
When k = 3, 6, 9..., the exponential terms sum to zero due to the 2Ï€ periodicity of complex phasors. This cancellation occurs without external filters, making zigzag configurations ideal for mitigating neutral currents in nonlinear loads.
Impedance to Zero-Sequence Currents
The zigzag connection presents high impedance to zero-sequence harmonics (dominant in switched-mode power supplies). The equivalent zero-sequence impedance Z0 is derived from the transformer's leakage reactance Xl and winding resistance R:
This impedance blocks zero-sequence circulation, forcing harmonic currents to cancel rather than propagate through the system. In practice, this reduces total harmonic distortion (THD) in voltage waveforms by 40–60% compared to delta-wye transformers.
Practical Implementation Considerations
- Winding Ratio Optimization: The turns ratio between zig and zag windings must be 1:1 to ensure symmetrical cancellation. Asymmetry allows residual harmonics to persist.
- Core Saturation: High harmonic content may drive the transformer into saturation if the core cross-section isn't oversized by at least 15% compared to standard designs.
- Parallel Operation: When used with active filters, zigzag transformers offload 70–80% of the harmonic filtering burden, reducing the filter's size and cost.
Case Study: Data Center Power Distribution
A 480V/208V zigzag transformer in a Tier IV data center reduced neutral current harmonics from 35% THD to 8% THD, eliminating the need for passive filters. The configuration also prevented neutral voltage rise, maintaining equipment safety margins within IEEE 519-2022 limits.
2.3 Phase-Shifting Properties
The phase-shifting capabilities of zigzag transformers arise from their unique winding configuration, which introduces a controlled angular displacement between primary and secondary voltages. Unlike conventional transformers, where phase shifts are fixed at 0° or 180°, zigzag arrangements enable adjustable phase displacements, making them invaluable in power systems requiring harmonic suppression or precise phase matching.
Mathematical Derivation of Phase Shift
The phase shift φ in a zigzag transformer is determined by the vectorial sum of voltages across interconnected windings. Consider a transformer with turns ratio N1:N2 and winding connections offset by 30° increments:
The zigzag secondary voltage Vab is derived from two 60°-offset winding segments:
This results in a net 30° phase advance relative to the primary. The generalized phase shift formula for k winding segments is:
Practical Implementation
In industrial applications, zigzag transformers achieve specific phase shifts through:
- Winding tap adjustments: Modifying the tap points changes the effective turns ratio and phase angle.
- Delta-zigzag connections: Provides 30° increments (e.g., ±30°, ±150°) for harmonic filtering in HVDC systems.
- Auto-transformer variants: Combines phase shifting with voltage transformation in compact designs.
Case Study: 12-Pulse Rectification
Two zigzag transformers with 15° and -15° shifts feed a rectifier bridge, creating 12-pulse operation that suppresses 5th and 7th harmonics. The phase displacement cancels characteristic harmonics through destructive interference:
where n is the harmonic order and Δφ is the phase shift between transformer outputs.
Frequency-Dependent Behavior
The phase shift exhibits frequency dependence due to:
- Leakage reactance variation with frequency
- Core loss tangent changes
- Winding capacitance effects at high frequencies
The normalized phase shift φn follows:
where φ0 is the nominal phase shift at reference frequency f0, and K is a topology-dependent constant.
3. Single-Phase Zigzag Configuration
Single-Phase Zigzag Configuration
The single-phase zigzag transformer configuration is a specialized arrangement primarily used for grounding and harmonic suppression in power systems. Unlike conventional single-phase transformers, the zigzag winding structure introduces a phase shift that enables unique neutral current handling and fault mitigation capabilities.
Winding Arrangement and Phasor Analysis
A single-phase zigzag transformer consists of two interconnected windings per phase, wound in opposite directions on the same core limb. The primary and secondary windings are split into two equal segments, with one segment wound in a zig (forward) direction and the other in a zag (reverse) direction. This creates a 60° phase displacement between the winding voltages.
The voltage phasors of the zigzag winding can be derived as follows:
Neutral Current Handling
The zigzag configuration excels at providing a low-impedance path for zero-sequence currents, making it ideal for grounding applications. Under balanced conditions, the neutral current is zero. However, during a ground fault, the transformer allows the fault current to return through the neutral without saturating the core.
The zero-sequence impedance (Zâ‚€) of the zigzag transformer is given by:
where Zleakage is the leakage impedance of each winding segment.
Harmonic Suppression
The zigzag connection inherently suppresses triplen harmonics (3rd, 9th, 15th, etc.) due to phase cancellation. This property is leveraged in power systems to mitigate harmonic distortion caused by non-linear loads.
Practical Applications
- Grounding Transformers: Used in ungrounded or delta-connected systems to provide a neutral point for grounding.
- Harmonic Filters: Integrated into industrial power systems to reduce triplen harmonics.
- Voltage Stabilization: Helps mitigate voltage unbalance in three-phase systems.
Case Study: Industrial Power System
In a 480V industrial plant with significant non-linear loads, a single-phase zigzag transformer was installed to suppress 3rd harmonic currents. Measurements showed a 72% reduction in harmonic distortion, improving power quality and reducing transformer losses.
The transformer was rated for:
Three-Phase Zigzag Configuration
The three-phase zigzag transformer configuration is primarily employed for grounding applications and harmonic mitigation in power systems. Unlike standard delta or wye configurations, the zigzag winding arrangement provides a low-impedance path for zero-sequence currents while maintaining high impedance for positive- and negative-sequence components.
Winding Structure and Phasor Analysis
Each phase of a zigzag transformer consists of two equal windings wound in opposite directions on the same core limb. For a three-phase system, the windings are interconnected such that the end of one phase's winding is connected to the start of another phase's winding in a zigzag pattern. This creates a phase shift of 60° between adjacent windings.
The voltage phasors of a balanced three-phase zigzag transformer can be derived as follows. Let Va, Vb, and Vc represent the phase voltages. The line-to-neutral voltage VLN is given by:
where VLL is the line-to-line voltage. The zigzag connection ensures that zero-sequence currents circulate within the transformer, providing effective grounding without a physical neutral connection.
Zero-Sequence Impedance
The zero-sequence impedance Z0 of a zigzag transformer is significantly lower than its positive-sequence impedance Z1. The relationship is given by:
This property makes zigzag transformers ideal for fault current limitation in ungrounded or resistance-grounded systems. The winding arrangement ensures that third-harmonic currents are trapped within the transformer, reducing harmonic distortion in the power system.
Practical Applications
- Grounding Transformers: Used in delta-connected systems to provide a neutral point for grounding.
- Harmonic Filtering: Suppresses triplen harmonics (3rd, 9th, etc.) in industrial power systems.
- Voltage Balancing: Mitigates voltage unbalance in systems with asymmetric loads.
In high-voltage applications, zigzag transformers are often paired with reactors or resistors to further control fault currents. Their compact design and efficiency in zero-sequence suppression make them a preferred choice in renewable energy systems and data center power distribution.
3.3 Autotransformer-Based Zigzag Designs
Autotransformer-based zigzag configurations offer a compact and cost-effective alternative to conventional zigzag transformers by sharing a portion of the winding between primary and secondary circuits. Unlike traditional designs requiring separate windings, autotransformers achieve voltage transformation through a single tapped winding, reducing copper losses and material costs while maintaining the desired phase-shifting properties.
Winding Configuration and Phasor Analysis
The autotransformer zigzag design consists of a three-limb core with interconnected windings arranged in a zigzag pattern. Each phase winding is divided into two sections: a common winding (Nc) and a series winding (Ns). The voltage relationship can be derived through phasor analysis:
where Vph is the phase voltage and the 30° phase shift arises from the vectorial subtraction inherent in the zigzag connection. The turns ratio between series and common windings determines the magnitude of neutral current compensation:
Advantages Over Conventional Designs
- Reduced copper weight: Only the series winding carries the full load current, while the common winding handles just the difference current.
- Lower leakage reactance: Tight magnetic coupling between windings improves voltage regulation.
- Smaller footprint: Elimination of separate secondary windings reduces core size by 15-20%.
Practical Implementation Considerations
When implementing autotransformer zigzag configurations, several design constraints must be addressed:
- Fault current limitation: The reduced impedance may require additional current-limiting reactors in high-fault scenarios.
- Harmonic suppression: Third-harmonic currents circulate more freely in autotransformer designs, often necessitating delta-connected tertiary windings.
- Voltage regulation: The inherent voltage drop across series windings must be compensated in sensitive applications.
Case Study: 34.5 kV Solar Farm Collector System
A 50 MW photovoltaic plant in Arizona employed autotransformer zigzag grounding transformers to handle unbalanced fault currents while minimizing capital costs. The design achieved:
with a 32% reduction in copper usage compared to conventional designs. Thermal imaging confirmed even temperature distribution across windings during 110% overload tests.
Mathematical Derivation of Neutral Current Compensation
The neutral current compensation capability stems from the winding arrangement's zero-sequence impedance. For a balanced system with ground fault current Ig:
where Z1, Z2, and Z0 represent positive, negative, and zero-sequence impedances respectively. The autotransformer configuration modifies the zero-sequence path such that:
This relationship demonstrates how proper winding ratio selection can optimize ground fault current levels while maintaining system stability.
4. Grounding and Neutral Current Compensation
4.1 Grounding and Neutral Current Compensation
Neutral Current Path in Zigzag Transformers
The zigzag transformer's unique winding arrangement provides a low-impedance path for zero-sequence currents while blocking positive and negative sequence components. The neutral point is created by connecting the zig and zag windings in series, with the common junction forming the neutral terminal. When unbalanced loads or ground faults occur, the transformer allows neutral current to flow while maintaining balanced phase voltages.
The zero-sequence impedance (Z0) of a zigzag transformer is significantly lower than its positive-sequence impedance (Z1), typically in the range of 1-5% of the base impedance. This relationship can be expressed as:
where Zleakage represents the leakage impedance of each winding section.
Grounding Applications
Zigzag transformers are particularly effective in:
- Ungrounded systems: Providing a grounded neutral point where none exists naturally
- Resistance-grounded systems: Limiting ground fault currents to safe levels
- Harmonic mitigation: Diverting triplen harmonics (3rd, 9th, etc.) to ground
Neutral Current Compensation
The transformer's ability to compensate for neutral current stems from its winding configuration. Each phase consists of two equal winding sections wound in opposite directions on different core legs. For a neutral current In, the current distribution in the windings becomes:
where subscripts 1 and 2 denote the two winding sections per phase. This equal distribution ensures that the magnetic fluxes in the core legs cancel out for zero-sequence currents, preventing core saturation.
Practical Implementation Considerations
When designing a zigzag transformer for grounding applications:
- The kVA rating must account for continuous neutral current requirements
- Winding insulation must withstand line-to-line voltage stresses
- Proper phase sequence (a-c-b or a-b-c) must be maintained during installation
- Neutral grounding resistor (NGR) sizing must coordinate with transformer impedance
Voltage Regulation Effects
The presence of neutral current affects voltage regulation differently for positive-sequence and zero-sequence components. The voltage regulation (VR) can be approximated by:
where VLL is the line-to-line voltage, θ is the impedance angle, and φ is the power factor angle.
Case Study: Industrial Plant Grounding System
A 13.8kV manufacturing facility experienced persistent ground faults due to an ungrounded distribution system. Implementation of a 500kVA zigzag transformer with 400A NGR reduced ground fault currents from several kiloamps to 200A, while maintaining service continuity during single-line-to-ground faults. The system voltage imbalance during faults was reduced from >15% to <3%.
4.2 Industrial Power Distribution Systems
Phase-Shifting and Harmonic Mitigation
Zigzag transformers are widely employed in industrial power distribution due to their inherent phase-shifting capabilities. The winding arrangement introduces a 30° phase displacement between primary and secondary voltages, making them particularly effective in canceling triplen harmonics (3rd, 9th, 15th, etc.). The phase shift arises from the geometric configuration of the windings:
where Np is the number of primary turns and Nz represents the zigzag winding turns. This displacement also aids in reducing circulating currents in parallel transformer configurations.
Grounding and Fault Current Management
In industrial systems with high fault currents, zigzag transformers provide a low-impedance path for zero-sequence currents while maintaining high impedance for positive and negative sequences. The zero-sequence impedance Z0 is derived as:
where Zp is the primary winding impedance and Zz the zigzag winding impedance. This property makes them ideal for:
- Limiting ground fault currents to <20% of phase fault levels
- Providing neutral grounding in ungrounded delta systems
- Mitigating ferroresonance in capacitor-coupled circuits
Voltage Unbalance Compensation
Industrial loads often cause voltage unbalance exceeding IEEE Std 1159-2019 limits. The zigzag transformer's negative-sequence impedance (Z2) is approximately 85-90% of its positive-sequence impedance (Z1), enabling superior unbalance compensation compared to star-delta transformers. The compensation factor Ku is given by:
Practical Implementation Considerations
When deploying zigzag transformers in industrial settings:
- Core saturation must be carefully analyzed due to DC offset during asymmetrical faults
- The K-factor rating should exceed 13 for nonlinear loads with THDi > 15%
- Optimal placement is typically at the PCC (Point of Common Coupling) for maximum harmonic filtering
4.3 Renewable Energy Integration
Zigzag transformers play a critical role in renewable energy systems by mitigating harmonic distortion, balancing unbalanced loads, and providing galvanic isolation. Their unique winding configuration enables efficient integration of distributed generation sources like solar photovoltaic (PV) arrays and wind turbines into the grid.
Harmonic Suppression in Inverter-Based Systems
Power electronic inverters in renewable energy systems introduce low-order harmonics due to switching operations. A zigzag transformer's phase-shifting properties attenuate triplen harmonics (3rd, 9th, 15th, etc.) by inducing opposing fluxes in its interconnected windings. The harmonic suppression capability can be quantified by analyzing the transformer's zero-sequence impedance (Z0).
where Zsc is the short-circuit impedance per phase and Zm is the magnetizing impedance. The high Z0 effectively blocks zero-sequence currents, which are predominant in inverter-generated harmonics.
Voltage Unbalance Compensation
Renewable sources often cause voltage unbalance due to intermittent generation and asymmetrical faults. The zigzag transformer's winding arrangement redistributes unbalanced currents, enforcing phase equilibrium. For a system with unbalanced voltages Va, Vb, and Vc, the corrected phase voltages (V'a, V'b, V'c) are derived as:
Case Study: Solar Farm Integration
A 50 MW solar farm in California employed zigzag transformers to address harmonic pollution from string inverters. Post-installation measurements showed a 72% reduction in total harmonic distortion (THD) and a 40% decrease in neutral current. The transformer's configuration also enabled seamless operation during single-line-to-ground faults, maintaining grid stability.
Design Considerations
- Winding Ratio: The turns ratio between zig and zag windings must be optimized for the expected harmonic spectrum.
- Core Saturation: High zero-sequence currents can drive the core into saturation, requiring careful selection of core material and geometry.
- Cooling Requirements: Harmonic currents increase eddy current losses, necessitating enhanced cooling systems in high-power applications.
5. Winding Arrangement and Impedance Matching
5.1 Winding Arrangement and Impedance Matching
The zigzag transformer derives its unique characteristics from its specialized winding configuration, which enables precise control over impedance transformation and harmonic suppression. Unlike conventional transformers, where windings are simply connected in series or parallel, the zigzag arrangement interleaves phases in a star or delta configuration with intentional angular displacement.
Winding Geometry and Phase Shift
Each limb of a zigzag transformer contains two equal winding sections with opposite polarity, connected to different phases. For a 3-phase system, this creates a 30° phase displacement between primary and secondary voltages. The winding ratio between sections determines the impedance transformation properties.
Where Van, Vbn, and Vcn represent the phase-to-neutral voltages on the secondary side, while Va, Vb, and Vc are the primary phase voltages.
Impedance Transformation Mechanism
The equivalent impedance seen from the primary side depends on both the turns ratio and the winding connection pattern. For a zigzag-delta configuration, the impedance transformation ratio becomes:
Where N1/N2 is the turns ratio between primary and secondary windings, and Zload is the secondary-side load impedance. The 3/2 factor arises from the vectorial combination of the interphase connections.
Practical Design Considerations
In industrial applications, zigzag transformers are often designed with:
- Unequal winding sections to create asymmetric impedance for fault current limitation
- Interleaved winding layers to reduce leakage reactance
- Precise angular displacement (typically 30° or 60°) for harmonic cancellation
The winding arrangement must account for skin and proximity effects at high frequencies, particularly when used in power electronic applications. Litz wire or subdivided conductors are often employed in high-current designs.
Impedance Matching Case Study
In a 12-pulse rectifier system, zigzag transformers provide the necessary 30° phase shift while matching the impedance between the AC source and diode bridges. The winding arrangement must satisfy:
where Zrectifier represents the equivalent impedance of the diode/capacitor network. Practical implementations often use dual secondary windings with a 1:√3 turns ratio to achieve both voltage transformation and impedance matching simultaneously.
5.2 Thermal Management and Efficiency
Thermal Behavior in Zigzag Transformers
Zigzag transformers exhibit unique thermal characteristics due to their winding geometry and harmonic suppression properties. The distributed winding arrangement leads to non-uniform current distribution, resulting in localized hotspots. The total power dissipation Ploss comprises resistive (I²R), core (Pcore), and stray losses (Pstray):
Core losses are minimized by using grain-oriented silicon steel, while stray losses arise from leakage flux interactions. The thermal resistance θth between the winding and ambient is given by:
where ΔT is the temperature rise. Forced air or oil cooling may be employed to maintain ΔT within safe limits (typically 65°C for dry-type transformers).
Efficiency Optimization Techniques
Efficiency η is defined as the ratio of output power to input power:
Key strategies for improving efficiency include:
- Winding Material Selection: High-conductivity copper or aluminum with minimal impurities reduces I²R losses.
- Core Design: Laminated cores with high permeability minimize hysteresis and eddy current losses.
- Harmonic Mitigation: Zigzag transformers inherently suppress triplen harmonics, reducing additional losses from non-sinusoidal currents.
Thermal Modeling and Simulation
Finite Element Analysis (FEA) is widely used to predict temperature distribution. The heat equation for a transformer winding is:
where k is thermal conductivity, q is heat generation rate, and Ïcp is volumetric heat capacity. Practical designs often use empirical derating curves to account for load variations.
Case Study: Industrial Zigzag Transformer
A 500 kVA zigzag transformer with 98.2% efficiency was analyzed under unbalanced loading. Hotspot temperatures were found to be 12°C higher than average winding temperatures due to circulating zero-sequence currents. Active cooling reduced the temperature gradient by 35%.
5.3 Protection Schemes and Fault Handling
Fault Current Analysis in Zigzag Transformers
Zigzag transformers exhibit unique fault current characteristics due to their winding configuration. Under a ground fault, the zero-sequence impedance (Z0) dominates the fault current path. The equivalent zero-sequence impedance can be derived as:
where Zn is the neutral grounding impedance and Zleakage represents the transformer's leakage impedance. This configuration inherently limits ground fault currents compared to conventional transformers.
Differential Protection Schemes
Conventional differential protection must be adapted for zigzag transformers due to phase-shifting effects. The operating principle relies on comparing currents at both ends of each winding segment:
Modern microprocessor-based relays implement compensation algorithms to account for the 30° phase shift between primary and secondary currents. Settings typically use 15-20% bias to prevent false tripping during magnetizing inrush.
Ground Fault Protection
The zero-sequence current path enables sensitive ground fault detection. Key methods include:
- Residual current monitoring via core-balance CTs on all three phases
- Neutral current measurement using a dedicated CT in the grounding path
- Directional ground relays for systems with multiple grounding points
Overcurrent Coordination
Time-current curves must account for the transformer's nonlinear impedance characteristics. The phase fault protection typically uses:
with time delays coordinated with downstream devices. For ground faults, settings of 10-20% of rated current are common due to the low zero-sequence impedance.
Thermal Protection Considerations
The unique winding arrangement affects heat distribution during unbalanced faults. Thermal models should incorporate:
- Non-uniform eddy current losses in interleaved windings
- Additional heating in the common neutral leg during ground faults
- Thermal time constants that vary with fault type
Practical Implementation Challenges
Field experience shows several common issues:
- CT saturation during high-magnitude ground faults due to DC offset
- False differential currents during transformer energization
- Coordination difficulties with downstream fuse-protected equipment
Modern solutions incorporate adaptive algorithms that dynamically adjust protection parameters based on real-time operating conditions.
6. Key Research Papers and Articles
6.1 Key Research Papers and Articles
- Analysis and Application of Zigzag Transformer in Distribution System ... — This paper present to reduce the harmonics currents and neutral overloading by using the zigzag transformer. The zigzag transformer is one of the solution to attenuate the neutral current and reduce the zero sequence harmonic currents of the distribution systems. ... Electronic ISBN: 978-1-7281-5371-1 DVD ISBN: 978-1-7281-5370-4 Print on Demand ...
- Novel Step-Up Topologies of Zigzag Autotransformer - MDPI — Zigzag autotransformer is widely used in multi-pulse rectifier system. However, the traditional zigzag autotransformer does not have the step-up function. Meanwhile, by improving the zigzag autotransformer structure, the output voltage can be increased without additional auxiliary components. Therefore, based on the 12 pulse rectifier system, this paper analyzes and designs three zigzag ...
- A review about Zig Zag Connections in Transformers - ResearchGate — According to international standards, the handling time for the short-circuit current is 2 to 3 seconds. However, in the case of the grounding transformer (zigzag transformer), the duration of the ...
- Autotransformer design with zig-zag connection Zna0 — The autotransformer which is supplied by network without neutral wire must be loaded symmetrically. Already small unsymmetrical load causes significant voltage imbalance and overvoltage. When the fully loading of one phase is required, the zigzag autotransformer connection must be used. This paper describes the behavior and design of autotransformers under unsymmetrical loading conditions.
- Power electronic zigzag transformer for experimental voltage generator ... — Abstract: This paper presents a mid-voltage experimental voltage generator used for the testing mainly of distribution power equipment, high-power drives and renewable power generation. It utilizes thyristor-controlled zigzag transformer as its primary circuit. Based on the analysis of the operation mechanism, the voltage equations are derived and control strategy is proposed.
- Novel Step-Up Topologies of Zigzag Autotransformer - ResearchGate — Therefore, based on the 12 pulse rectifier system, this paper analyzes and designs three zigzag autotransformer step-up topologies, establishes the corresponding mathematical topology, studies the ...
- A review about Zig Zag and Double Zig Zag connections in Transformer — Whenever we think of three-phase transformer connections, we think straightaway of either star-connected transformers or delta-connected transformers. A great majority of polyphase transformers are either in series or connected in delta. In either case, the connection is symmetrical or balanced. In this paper, the winding connections, the voltage distribution in the windings, the application ...
- (PDF) Investigation of the usage of zigzag transformers to reduce ... — Based on the results of this research, the total harmonic distortion (THD) value has decreased from 25.26 % to 2.48 % following the implementation of the zigzag transformer.
- Threeâ€phase four switch DSTATCOM topologies with special transformers ... — Therefore, in this paper, four different DSTATCOM topologies are proposed by combining FSSC or FSOC inverter configuration with a zigzag or T-connected transformer. FSSC or FSOC inverter configuration is responsible for the compensation of phase-current harmonics, reactive power produced by the load, also reduces the number of power devices and ...
- A review about Zig Zag and Double Zig Zag connections in Transformer — a two-winding transformer with one Zig-zag winding cannot be used.Since it is a polyphase system, with each leg having windings from 2 different phases, the system has to be resolved
6.2 Industry Standards and Guidelines
- PDF Overview of IEC/TS 60076-20 Ed. 1.0: Power Transformers - Part 20 ... — Traction transformers for 16.7 Hz Earthing transformers following IEC60076-6 Transformers which cannot fulfil the energy performance requirements due to unavoidable size and weight limitations In this standard 'transformers' includes both separate winding transformers and autotransformers.
- C57.105-2019 - IEEE Guide for Application of Transformer ... - IEEE Xplore — Scope: This guide describes transformer connections and configurations in three-phase electrical systems, the characteristics of these various connections, and the possible operating problems under normal or abnormal conditions. All combinations of delta and wye, grounded and ungrounded, T-connected, zigzag, and certain special connections are considered. Only two-winding and auto-transformers ...
- PDF IEEE Guide for Application of Transformer Connections in Three-Phase ... — IEEE SA Standards Board his guide describes transformer connections and configurations in three-phase electrical systems. The characteristics of the various transf rmer connections and possible operating problems under normal or abnormal conditions are treated. All combinations of delta and ye, grounded and ungrounded, T-connected, zigzag, an
- Zig-Zag Transformer Application in 20 KV System - Scribd — This document discusses the application of a zig-zag transformer in the 20kV electrical system of an HMS plant in Pasuruan, Indonesia. It describes the plant's normal and island operation schemes, the need for a grounding transformer when operating in isolated mode, and the objectives, sizing, protection settings, and recommendations for implementing a zig-zag transformer to provide a neutral ...
- IEEE SA - IEEE C57.105-1978 - standards.ieee.org — These systems are characterized by primary voltages up to and including 34.5 kV, usually have a preponderance of connected transformers with low-voltage windings below 1000 V, and furnish electric service to consumers. All combinations of Delta and Y, grounded and ungrounded, T connected, zigzag, and certain special connections are considered.
- Zig-zag transformer applications and calculations — A 600-volt zig-zag transformer is a type of special-purpose transformer primarily used for grounding and neutral creation in three-phase electrical systems. The zig-zag winding arrangement provides unique capabilities that make it suitable for handling specific tasks in distribution and industrial systems.
- PDF Comparison of Loading Guide Standards IEEE and IEC — documents and all documents are "standards". Accordingly, whereas in IEEE the Loading Guide is an informative guide, in IEC the Loading Guide is a normative standard. In the next revision, the te
- PDF NG301-07ZigZag_Grounding_Transformers — The transformer shall be a three-phase, dry-type, air-cooled auto-transformer with each phase having two windings connected in a Zigzag configuration. It shall have class "B" insulation up to 2400 volts or class "H" insulation above 2400 volts.
- ZigZag Transformer Connection Overview - EEP — We rarely use zigzag configurations for typical industrial or commercial use, because they are more expensive to construct than conventional Star connected transformers. But zigzag connections are useful in special applications where conventional transformer connections aren't effective.
- PDF GT210-10_Zigzag_Trans_pg1 - postglover.com — The Zigzag grounding transformer is a commonly used option. It is a three-phase, dry-type, air- cooled auto-transformer with no secondary winding. Each phase has two identical windings, which are wound in opposite directions to give the high impedance to normal phase currents. The windings are connected in a Wye configuration. The neutral point is then connected either directly or through a ...
6.3 Recommended Books and Technical Manuals
- C57.105-2019 - IEEE Guide for Application of Transformer ... - IEEE Xplore — This guide describes transformer connections and configurations in three-phase electrical systems. The characteristics of the various transformer connections and possible operating problems under normal or abnormal conditions are treated. All combinations of delta and wye, grounded and ungrounded, T-connected, zigzag, and certain special connections are considered. Only two-winding and auto ...
- GE T35 INSTRUCTION MANUAL Pdf Download | ManualsLib — View and Download GE T35 instruction manual online. Transformer Management Relay. T35 relays pdf manual download. ... It performs this function on a variety of power transformer configurations with up to six sets of three phase inputs available. ... TRANSFORMER WINDING CONNECTION 0 = Wye, 1 = Delta, 2 = Zig-zag F164 ENUMERATION: TRANSFORMER ...
- Transformer Design Principles, Third Edition - 3rd Edition - Routledge — 7.8 Zig-Zag Transformer . 8 MULTI-TERMINAL THREE PHASE TRANSFORMER MODEL . 8.1 Introduction . ... This book focuses on providing an understanding of the technical details of designing traditional single-phase and multiphase power transformers. In this latest edition, which still includes fundaÂmental design equations and theory used to design ...
- Zig Zag Transformer | PDF | Transformer | Electrical Impedance - Scribd — Zig Zag Transformer - Free download as Word Doc (.doc), PDF File (.pdf), Text File (.txt) or read online for free. This document specifies the requirements for a zig-zag grounding transformer to limit ground fault current on a 34.5 kV system. It outlines the calculations to determine that a 6.3 ohm/phase zig-zag grounding transformer is needed to limit the ground fault current to 5500 amps, as ...
- PDF Zigzag Grounding Transformers - Post Glover Resistors — Transformer The transformer shall be a three-phase, dry-type, air- cooled auto-transformer with each phase having two windings connected in a Zigzag configuration. It shall have class "B" insulation up to 2400 volts line to neutral or class "H" insulation above 2400 volts. The transformer shall be continuously rated for the
- Zig-Zag Transfomers - Electric power & transmission ... - Eng-Tips — Zig-zag transformers are rarely purchased any longer (in the US) so technical info will be hard to come by. If you have access to Edith Clarke's books, those would be helpful as well. But these are long out of print. ... The J&P Transformer Book, (12th edition - Martin J. Heathcote) also briefly discuss zigzag transformers. ...
- ABB RET650 APPLICATIONS MANUAL Pdf Download | ManualsLib — A common application is for low reactance earthed transformer where the earthing is through separate zig-zag earthing transformers. The fault current is then limited to typical 800 to 2000 A for each transformer. ... Page 219 Manual configuration of VCTR GOOSE data set is required. Note that both data value attributes and quality attributes ...
- PDF IEEE Guide for Application of Transformer Connections in Three-Phase ... — Transformer Connections in Three-Phase Electrical Systems IEEE Power and Energy Society Developed by the Transformers Committee IEEE Std C57.105™-2019 (Revision of IEEE Std C57.105-1978) This is a preview of "IEEE C57.105-2019". Click here to purchase the full version from the ANSI store.
- Zig-Zag Transformer for Grounding System - PSCAD — Transformers; Zig-Zag Transformer for Grounding System. Lastest update: February 20, 2022. This example discusses the use of the zig-zag transformers in a power system to provide a high impedance ground system for the delta connected or ungrounded power systems.